INSTALLING THE OUTDOOR UNIT
Connecting the Cables to the Outdoor Unit(Continued)
MH080FX
A4
1(L) 2(N) 1(L) 2(N)
F1 F2 F1 F2
L
N
1(L) 2(N) F1 F2
1(L) 2(N) F1
1(L) 2(N) F1
1(L) 2(N) F1
F2
1 2
1 2
F1 F2
F1 F2
F1 F2
F1 F2
1 2
2
1
F2
1 2
F1 F2
F1 F2
F2
F1 F2
F1 F2
1 2
2
1
1 2
1
2
B
C
B
C
B
C
B
C
A
A
B
C
D
A
B
F1 F2 F1 F2
C
D
1(L) 2(N) 1(L) 2(N)
A-unit
B-unit
C-unit
D-unit
Indoor unit
Assembly cable
Outdoor unit
Earth
terminal
Earth
terminal
Earth
terminal
Earth
terminal
Earth
terminal
Earth
terminal
Earth
terminal
Earth
terminal
Power cable to indoor units
Earth
terminal
Main Power
supply cable
Communication cable
to indoor units
�
�
�
Cable Type: A
Cable Type: B
Cable Type: C
The specification for cables :
Connect the power cable to the auxiliary circuit breaker.
If every pole fails to connect to the power supply, it must be
incorporated in a wire with a contact opening of ≥0.12 inch.
Model
Main Power Supply Cable Indoor Power Supply Cable
Communication Cable
FUSE
MCCB
Type GL
Specication
Type
Specication
Type
Specication
Type
MH050FX*A2*
3G, 2.5mm2 or
more,
H07RN-F
�
3G, 1.0mm2 or
more,
H07RN-F
�
2G, 0.75mm2 or
more,
H07RN-F
�
20A
Frame : 30A
Trip : 20A
20A
MH080FX*A4*
30A
Frame : 30A
Trip : 30A
30A