![Samsung MCU-Y6NEE Installation Manual Download Page 21](http://html1.mh-extra.com/html/samsung/mcu-y6nee/mcu-y6nee_installation-manual_3775651021.webp)
21
Setting MCU option
DIP switch for indoor unit setting (ON:Use, OFF:Not use)
Rotary switch for MCU ADDRESS
Rotary switch for Indoor unit ADDRESS
• Connect the power cable using the compressed ring terminal.
MCU
MCU
Indoor unit
Indoor unit
Indoor unit
Indoor unit
Indoor unit
Indoor unit
Indoor unit
Indoor unit
Indoor unit
Indoor unit
Indoor unit
Indoor unit
MCU
MCU
• Communication cables are connected as shown above when installing MCU.
• When installing electricity and wires of MCU, please proceed the work refering to the installation manual of the
HR outdoor unit.
How to set up
Set the rotary switch located at outdoor unit PCB to match the number of connected indoor units (8).
Set the rotary switch located at outdoor unit PCB to match the number of connected MCU (2).
When installing more than 2 MCUs, set each rotary switch of MCU differently.
Set rotary switch located at MCU PCB to match indoor unit address.
Set the DIP switch of MCU to “OFF” position for the indoor units that is not connected.
Setting the
number of
Indoor Unit
Outdoor Unit
PCB
MCU PCB
MCU PCB
Indoor unit address
MCU address
Indoor unit address
Indoor unit
Indoor unit
Setting the
number of
MCU
MCU address
MCU-Y6NEE_IM_E 33933A(1).indd 21