5. Select the insulation of the refrigerant pipe.
Insulate the gas side and liquid side pipe referring to the thickness according to the pipe size.
Indoor temperature of 30°C and humidity of 85% is the standard condition. If install in a high humidity condition, use one grade thicker
insulator by referring to the table below. If installing in an unfavorable conditions,use thicker one.
Insulator’s heat-resistance temperature should be more than 120°C.
Pipe
Pipe size
Insulation Type(Heating/Cooling)
Remarks
Standard
[30°C, 85%]
High humidity
[30°C, over85%]
EPDM, NBR
Liquid
pipe
ø
6.35~
ø
9.52
9t
9t
Internal temperature
is higher than 120°C
ø
12.70~
ø
50.80
13t
13t
Gas
Pipe
ø
6.35
13t
19t
ø
9.52
19t
25t
ø
12.70
ø
15.88
ø
19.05
ø
22.23
ø
25.40
ø
28.58
32t
ø
31.75
ø
38.10
ø
44.45
ø
50.80
25t
38t
Refrigerant pipe before EEV kit and MCU or without EEV kit and MCU
You can contact the gas side and liquid side pipes but the pipes
should not be pressed.
When contacting the gas side and gas side pipe, use 1 grade thicker
insulator.
Refrigerant pipe after EEV kit and MCU
Install the gas side and liquid side pipes, leave 10mm of space.
When contacting the gas side and liquid side pipe, use 1 grade
thicker insulation.
Gas pipe
Liquid pipe
Insulation
Insulation
Gas pipe
10mm
Liquid pipe
10mm
10mm
10mm
•
Install the insulation not to get wider and use the adhesives on the connection part of it to
prevent moisture from entering.
•
Wind the refrigerant pipe with insulation tape
if it is exposed to outside sunlight.
•
Install the refrigerant pipe respecting that the
insulation does not get thinner on the bent
part or hanger of pipe.
• Add the additional insulation
if the insulation plate gets thinner.
Additional insulation
Hanger
Refrigerant pipe insulation
a×3
a