208/230V
System
Breaker
Separate all Power &
Communications Wiring by 2”
Indoor Unit
(Ground)
Outdoor
Unit
F2
F1
G
L1
L2
F2
F1
G
L1
L2
POWER VOLTAGE:
Power Voltage:
208/230V - 1 Ph - 60 Hz
Control Voltage:
DDC Fuzzy Logic
Main Breaker Size:
20 A
CHARGING:
Unit is charged for:
25 ft. (Factory Charge 58.1oz. R410A)
Additional Charge of R410A:
0.16 oz./ft. over 25 ft.
CHARGE FOR LINE RUN LENGTHS:
Length:
25
35
45
55
65
75
85
95
98
Added Charge (oz.):
0
1.6
3.2
4.8
6.4
8.0
9.6 11.2 11.68
INTERCONNECTING WIRING:
Gauge:
14 AWG Power & 16 AWG Shielded Communication
Number of Interconnecting Wires: 3x14 AWG Power & 2x16 AWG Control = 5 Total
LINE SIZES:
“Liquid” (expanded gas) line:
1/4”
Suction:
5/8”
BOTH LINES MUST BE INSULATED SEPARATELY
Samsung MAX 24,000 BTU Mini-Split
Indoor Unit: #700554 (AQN24VFUAGM)
Outdoor Unit: #700556 (AQX24VFUAGM)
INTERCONNECT LENGTH:
Maximum/Minimum Length:
98 feet / 10 feet
Vertical Lift:
50 feet (Trap required at 26 ft.)
Note: Condenser can be above or below evaporator