Model  : AM***BXVTFH/AA, AM***BXVTJH/AA

VRF

Technical 

Data Book

Max Heat DVM S2 for America

(R410A, 60Hz, HP)

Summary of Contents for Max Heat DVM S2

Page 1: ...Model AM BXVTFH AA AM BXVTJH AA VRF Technical Data Book Max Heat DVM S2 for America R410A 60Hz HP...

Page 2: ...Version Modification Date Remark Ver 1 0 Release Max Heat DVM S2 HP TDB for America 23 12 20 History...

Page 3: ...ter 6 Feature 2 A Standard General Temp Module H High EER Low Temp Module G High EER General Temp Module D Standard General Temp Non Module 7 Rating Voltage 8 Mode H Heat Pump R Heat Recovery OutdoorU...

Page 4: ...ligent features make installation and maintenance easier and more cost effective Perfectly compatible with WindFree Active Frequency Drive 10Hz Enjoy continuous comfort and avoid wasting energy Active...

Page 5: ...st capacity It combines Flash Injection technology with a strengthened Triple Profile Scroll and efficient Optimal Discharge Superheat DSH Control technology Samsung circulates 14 400cc sec refrigeran...

Page 6: ...Combination Table Design Procedure Combination Ratio 2 Specification 3 Electric Characteristics 4 Dimensional Drawing 5 Center of Gravity 6 Electrical Wiring Diagrams 7 Sound Data 8 Operation Range 9...

Page 7: ...m design Refer to the Design Procedure Combination Ratio section of this document for details You can connect maximum 64 indoor units to the outdoor unit Maximum quantity of connectable indoor unit is...

Page 8: ...dard allowed combination ratio of the total rated indoor unit capacity over the rated outdoor unit capacity is 50 130 Combination ratio of up to 184 is allowed depending on operation mode minimum oper...

Page 9: ...ON Model Name Model 6 8 10 External Appearance 1 Combination Table Outdoor units AM072BXVTFH AA AM096BXVTFH AA AM120BXVTFH AA 12 14 16 AM144BXVTFH AA AM168BXVTFH AA 18 20 AM192BXVTFH1AA 22 AM264BXVTFH...

Page 10: ...el 6 8 10 External Appearance 1 Combination Table Outdoor units AM072BXVTJH AA AM096BXVTJH AA AM120BXVTJH AA 12 14 16 AM144BXVTJH AA AM168BXVTJH AA 18 20 AM192BXVTJH1AA 22 AM264BXVTJH AA 24 AM288BXVTJ...

Page 11: ...necessaryto design a combination ratio exceeding130 the following conditions must be complied with Design Selection Procedure Determine DVM Design Condition Design temperature Calculate cooling and he...

Page 12: ...e Peak Loads at 14 00 61 0kW When a system combination ratio is over130 a max system capacity is the same as the published capacity in TDB capacity table at the combination ratio of 130 NOTE Cooling O...

Page 13: ...capacity of indoor units running in both cooling heating mode 100 Sum of nominal capacity of indoor units The Minimum Operation Ratio should be determined during the project design stage using Fig 2...

Page 14: ...including abnormal noise that arises during heating operation due solely to the operation rate being lower than the designated combination ratio shown in Fig 2 Please contact your local Samsung repre...

Page 15: ...x 2 Inverter Scroll x 2 Output kW x n 4 39 x 2 6 45 x 2 6 45 x 2 Model Name DS2GT7046EV x 2 DS4GT5066EV x 2 DS4GT5066EV x 2 Oil Type PVE PVE PVE Initial charge cc x n 900 x 2 1 100 x 2 1 100 x 2 fl o...

Page 16: ...the rated outdoor unit capacity is 50 130 Combination ratio of up to 184 is allowed depending on operation mode minimum operation ratio and connected indoor unit models DVM Pro 2 design software suppo...

Page 17: ...oll x 4 Output kW x n 4 39 x 2 x 2 4 39 x 2 x 1 6 45 x 2 x 1 6 45 x 2 x 2 Model Name DS2GT7046EV x 2 x 2 DS2GT7046EV x 2 x 1 DS4GT5066EV x 2 x 1 DS4GT5066EV x 2 x 2 Oil Type PVE PVE PVE Initial charge...

Page 18: ...The standard allowed combination ratio of the total rated indoor unit capacity over the rated outdoor unit capacity is 50 130 Combination ratio of up to 184 is allowed depending on operation mode min...

Page 19: ...kW x n 4 39 x 2 x 3 4 39 x 2 x 2 6 45 x 2 x 1 4 39 x 2 x 2 6 45 x 2 x 1 Model Name DS2GT7046EV x 2 x 3 DS2GT7046EV x 2 x 2 DS4GT5066EV x 2 x 1 DS2GT7046EV x 2 x 2 DS4GT5066EV x 2 x 1 Oil Type PVE PVE...

Page 20: ...ation ratio of the total rated indoor unit capacity over the rated outdoor unit capacity is 50 130 Combination ratio of up to 184 is allowed depending on operation mode minimum operation ratio and con...

Page 21: ...1 6 45 x 2 x 2 Model Name DS2GT7046EV x 2 x 1 DS4GT5066EV x 2 x 2 Oil Type PVE Initial charge cc x n 900 x 2 x 1 1 100 x 2 x 2 fl oz x n 30 4 x 2 x 1 37 2 x 2 x 2 Fan Type Propeller Dischargedirectio...

Page 22: ...indoor unit models DVM Pro 2 design software supports designing over 130 based on system design Refer to the Design Procedure Combination Ratio section of this document for details 3 IIf outdoor unit...

Page 23: ...erter Scroll x 2 Output kW x n 4 39 x 2 6 67 x 2 6 67 x 2 Model Name DS2GR7046FV x 2 DS4GR7066FV x 2 DS4GR7066FV x 2 Oil Type PVE PVE PVE Initial charge cc x n 900 x 2 1 100 x 2 1 100 x 2 fl oz x n 30...

Page 24: ...he rated outdoor unit capacity is 50 130 Combination ratio of up to 184 is allowed depending on operation mode minimum operation ratio and connected indoor unit models DVM Pro 2 design software suppor...

Page 25: ...Output kW x n 4 39 x 2 x 2 4 39 x 2 x 1 6 67 x 2 x 1 6 67 x 2 x 2 Model Name DS2GR7046FV x 2 x 2 DS2GR7046FV x 2 x 1 DS4GR7066FV x 2 x 1 DS4GR7066FV x 2 x 2 Oil Type PVE PVE PVE Initial charge cc x n...

Page 26: ...he standard allowed combination ratio of the total rated indoor unit capacity over the rated outdoor unit capacity is 50 130 Combination ratio of up to 184 is allowed depending on operation mode minim...

Page 27: ...4 39 x 2 x 3 4 39 x 2 x 2 6 67 x 2 x 1 4 39 x 2 x 2 6 67 x 2 x 1 Model Name DS2GR7046FV x 2 x 3 DS2GR7046FV x 2 x 2 DS4GR7066FV x 2 x 1 DS2GR7046FV x 2 x 2 DS4GR7066FV x 2 x 1 Oil Type PVE PVE PVE Ini...

Page 28: ...ion ratio of the total rated indoor unit capacity over the rated outdoor unit capacity is 50 130 Combination ratio of up to 184 is allowed depending on operation mode minimum operation ratio and conne...

Page 29: ...ressor Type Inverter Scroll x 6 Output kW x n 4 39 x 2 x 1 6 67 x 2 x 2 Model Name DS2GR7046FV x 2 x 1 DS4GR7066FV x 2 x 2 Oil Type PVE Initial charge cc x n 900 x 2 x 1 1 100 x 2 x 2 fl oz x n 30 4 x...

Page 30: ...ndoor unit models DVM Pro 2 design software supports designing over 130 based on system design Refer to the Design Procedure Combination Ratio section of this document for details 3 IIf outdoor unit i...

Page 31: ...76 0 90 0 4 2 4 2 76 0 90 0 Capacity Model Name Power Supply Module 1 Module 2 Module 3 FLA A MCA A MOP A FLA A MCA A MOP A FLA A MCA A MOP A TON Hz Voltage FAN1 FAN2 FAN1 FAN2 FAN1 FAN2 6 AM072BXVTJ...

Page 32: ...Liquid Ref pipe See NOTE 4 6 Knock out Hole forRef Piping front 3 Powerwiring conduit 44 4 Communication wiring conduit 34 NOTE 1 Detail A and SECTION B B indicate the dimension after fixing the attac...

Page 33: ...Outdoorunit 5 Centerof Gravity C A Foundation bolt hole B Model A B C Unit mm inches AM072BXVT H AA AM096BXVT H AA AM120BXVT H AA 324 12 3 4 520 20 1 2 678 26 11 16...

Page 34: ...RSSOR2 Motor compressor2 AIR 10K Thermistor Ambient Temp _10Kohm OD EEV V V Electronic expansion valve Outdoor EEV FAN1 Motor fan1 COND 10K Thermistor Cond Out Temp _10Kohm F101 FUSE INV PCB FAN2 Moto...

Page 35: ...ermistor Ambient Temp _10Kohm OD EEV V V Electronic expansion valve Outdoor EEV COMPRSSOR2 Motor compressor2 AIR 10K Thermistor Cond Out Temp _10Kohm F101 FUSE INV PCB FAN1 Motor fan1 COND 10K Thermis...

Page 36: ...NC 55 NC 50 NC 45 NC 40 NC 35 NC 30 NC 25 NC 20 NC15 90 85 80 75 65 60 55 50 45 40 35 30 25 20 15 10 5 0 63 250 125 500 2000 1000 8000 4000 Silent 3 Hearing threshold Silent 2 Silent 1 Cooling Heatin...

Page 37: ...eshold Silent 2 Silent 1 Cooling Heating 90 85 80 75 65 60 55 50 45 40 35 30 25 20 15 10 5 0 NC 70 NC 60 NC 55 NC 50 NC 45 NC 40 NC 35 NC 30 NC 25 NC 20 NC15 8000 90 85 80 75 65 60 55 50 45 40 35 30 2...

Page 38: ...Center Frequency Hz NC 70 NC 60 NC 55 NC 50 NC 45 NC 40 NC 35 NC 30 NC 25 NC 20 NC 15 0 5 10 15 20 25 30 35 40 45 50 55 60 65 70 75 80 85 90 95 100 105 110 0 5 10 15 20 25 30 35 40 45 50 55 60 65 70...

Page 39: ...50 500 1000 2000 4000 8000 A Sound Power Level dB Octave Band Center Frequency Hz 0 5 10 15 20 25 30 35 40 45 50 55 60 65 70 75 80 85 90 95 100 105 110 A NC 70 NC 60 NC 55 NC 50 NC 45 NC 40 NC 35 NC 3...

Page 40: ...cooling operating is possible under expand operational range only for HR system 4 In case of heatlng mode operating is possible underwarming up operation range However continus opearting is impossibl...

Page 41: ...Outdoor temperature F DB 0 99 Capacity coef cient of outdoor unit on defrost operation 0 98 0 96 0 95 0 91 0 88 0 86 0 91 1 00 On heating operation frost can be formed on heat exchanger according to...

Page 42: ...r Suction pipe T_S Pressure Sensor Low PS_L Pressure SolenoidValve Sensor SolenoidValve 4Way2 V_4W2 High1 4Way V_4W PS_H1 CheckValve Solenoid Valve Discharge1 CV_D2 HotGasbypass CV_D1 V_HG Solenoid Va...

Page 43: ...1 Do not install the product in a place where it is directly exposed to sea water and sea breeze Make sure to install the product behind a structure such as building that can block see breeze Even whe...

Page 44: ...an area with weak electromagnetic waves and put the main power cable and communication cables in a separately installed protection tube Make sure that there is no equipment that generates electromagne...

Page 45: ...ecause the refrigerant running of MCU may create noise Outdoor unit space requirements Space requirement was decided based on following conditions Cooling mode outdoor temperature of 35 C 95 F Larger...

Page 46: ...n value h1 h2 additional clearance h1 2 h2 2 Half of the exceeded height should be added to the service space S1 S2 Unit mm inch Case 3 Over 500 20 Over 500 20 Over 600 24 Over100 4 Over100 4 Over100...

Page 47: ...listed in above table and do not use imitated accessories Classification Model Name Specification MBH kW Y Joint Only H R MXJ YA1500M 76 and below 22 4 and below MXJ YA2500M MXJ YA3100M MXJ YA3800M O...

Page 48: ...the wind speed of 30m s If you cannot fix the outdoor unit on the base ground fix it by side or use extra structure 5 In heating operation defrost water may form so you must really care about the dra...

Page 49: ...for connecting the anti vibration pad Unit mm inch Base ground Hbeamoranti vibration frame Over 200 8 Over 200 8 Over 50 2 Outdoorunitinstallation Unit mm inch Classification DVM S2 Large type A 1 295...

Page 50: ...ear the installation space When the outdoor unit is installed on the roof check the strength and waterproof status of the roof Unit mm inch 960 37 80 760 29 92 100 3 94 80 3 15 80 3 15 80 3 15 6 0 120...

Page 51: ...r unit on the rooftop check the strength and make sure to waterproof the rooftop Construct draining pit around the base construction and pay attention to the drainage around the outdoor unit Condensat...

Page 52: ...gn substance may enter into the product and there could be a risk of personal injury Wear protection equipment at all times when making galvanized sheet metal duct since the orker may get injured by t...

Page 53: ...ay accumulate if the area of the frame or the base ground is larger hh Installing the outdoor unit in windy region In windy regions such as near sea shores protection wall or wind protection duct must...

Page 54: ...52 36 558 21 97 871 34 29 2413 95 345 13 58 723 28 46 723 28 46 464 18 27 180 7 09 980 38 58 668 26 3 532 20 94 567 22 32 765 30 12 540 21 26 180 7 09 953 37 52 1123 44 21 2271 89 41 1150 45 28 1632 6...

Page 55: ...erant pipe and there shouldn t be any harmful ion oxide dust iron content or moisture inside pipe Use tools and accessories that fit on R 410A only Installation process Compatibilitywith Tool purpose...

Page 56: ...igerant pipe according to main pipe size of each outdoor unit capacity When the pipe length including elbow between an outdoor unit and the farthest indoor unit exceeds 90m 295ft you must increase the...

Page 57: ...ed to the outdoor unit A apply the pipe size A Indoorunit capacity MBH Indoorunit capacity kW Branchpipelengthwithin 148ft 45m Branchpipelengthbetween 148ft 295ft 45 90m Liquid Gas Liquid Gas inch mm...

Page 58: ...9 52 3 8 50 164 12 7 1 2 200 656 12 9 52 3 8 30 98 12 7 1 2 160 525 14 12 7 1 2 90 295 15 88 5 8 200 656 16 12 7 1 2 90 295 15 88 5 8 200 656 18 12 7 1 2 80 262 15 88 5 8 200 656 20 12 7 1 2 60 197 1...

Page 59: ...harging is 0 0067lb ft 0 01kg m regardless of the pipe size 1 2 5m 16 4 1 2 5m 16 4 1 2 5m 16 4 1 4 5m 16 4 1 4 10m 32 8 1 4 15m 49 2 3 8 10m 32 8 3 8 10m 32 8 3 8 10m 32 8 3 8 10m 32 8 1 4 5m 16 4 3...

Page 60: ...nding AM NFDCH AM NGDCH 0 26 0 12 0 49 0 22 0 49 0 22 0 71 0 32 0 71 0 32 Ceiling AM NCDCH 0 86 0 39 0 86 0 39 1 23 0 56 2 09 0 95 MPAHU V AHU AM NZDCH 0 73 0 33 1 10 0 50 1 10 0 50 1 83 0 83 1 94 0 8...

Page 61: ...d pipe 6 35 1 4 35 114 8 0 02 0 013 0 7 1 49 5 575 12 19 9 52 3 8 50 164 0 0 06 0 040 3 0 6 56 12 70 1 2 15 49 2 0 125 0 084 1 875 4 13 Classification Model name of indoorunit Numberofindoorunits Unit...

Page 62: ...re to prevent any damages on the exterior of the outdoor unit Remove all burrs around the knock out hole and apply varnish on the cross section and edges of the knock out hole to prevent rust Use a ca...

Page 63: ...the sealed pipe on the bottom side of the service valve cut it with a pipe cutter rst and then start the welding When the sealed pipe is welded without cutting you may get injured by the refrigerant w...

Page 64: ...tdoor units Check the changes in comparison with the DVM and Caution Correct installation Incorrect installation Refrigerant pipes should be connected at the same orlower level than the ones connected...

Page 65: ...Refrigerantpipeinstallation 10 Installation Examples of refrigerant pipe installation 1 Using Y joint 2 Usingdistribution header...

Page 66: ...ribution header a b c d e f g h i j k Installing only with distribution header a b c d e f g h i Outdoor Outdoor unit Module installation Pipe length 10 m 33 or less x z y Equivalent length 13 m 43 or...

Page 67: ...Y joint and distribution header Installing only with distribu tion header Note1 Required conditions must be satisfied EEV kit Model name Remarks kk Actual pipe length 2m 6 6 MEV E24SA 1 indoor Apply t...

Page 68: ...e connection welding Liquid pipe connection welding 70 mm When installing MCU use the pattern sheet for installation that is provided with the product When welding the gas pipes protect the product wi...

Page 69: ...4 2 4 2 50 60 18 18 4 2 4 2 50 60 28 28 4 2 4 2 76 90 24Ton AM288BXVTF 60 208 230 18 18 4 2 4 2 50 60 22 22 4 2 4 2 62 70 28 28 4 2 4 2 76 90 Module 1 Module 2 Nom Units RLA FLA Power Supply RLA FLA...

Page 70: ...r o not use the ower cable with the core wire e osed due to insulator damage occurred during remo al of the sheath hen the core wire is e osed it ma cause fire Insulator innercover Exposedwire core Th...

Page 71: ...n the illustration Name Tempergrade Applicable conditions When the protection tube is installed indoorand not exposed to outside because it is embedded in concrete structure Flexible PVC conduit PVC W...

Page 72: ...er checking that R S T 3 phase 3 wire is properly connected Malfunction may occur if one or more of the wires among R S T phases 3 Phases 3 Wires are not connected properly Malfunction Turing on off o...

Page 73: ...2 17 5 1 2 Allowance mm inch 0 3 0 011 0 2 0 007 0 3 0 011 0 2 0 007 0 3 0 011 0 2 0 007 0 5 0 019 0 2 0 007 0 5 0 019 0 2 0 007 0 5 0 019 0 2 0 007 0 5 0 019 0 4 0 015 d1 Standard dimension mm inch 3...

Page 74: ...he thin cable upward and the thick cable downward Fix the power cablewith a cable tie Solderless ring terminal Cable tie 1 Front connection 10 Installation Connecting the power terminal 2 Closing the...

Page 75: ...he vibration of the compressor is transferred to the pipes and can damage the power supply cables or pipes creating the danger of fire or explosion Make sure that the place where the sheath of power s...

Page 76: ...ation fix it with cable tie 3 Fix the housing which has an insulator to the terminal board Fixing the ground cable Grounding Connect the ground cable to the grounding hole inside the power supply box...

Page 77: ...2 OF1 OF2 R1 R2 Terminal block with indoorunit Terminal block with outdoor unit sub module Terminal block with solution device A Where to install the interface module Install the interface module in l...

Page 78: ...3 50 3 34 3 74 3 54 2 05 2 15 AM288BXVTFH 274 000 308 000 11 50 11 50 24 80 21 30 23 05 3 28 3 60 3 44 2 05 2 13 AM072BXVTJH 69 000 77 000 13 10 12 70 28 30 23 70 26 00 4 30 4 14 4 22 2 58 2 46 AM096B...

Page 79: ...ead Of ce Suwon Korea 129 Samsung Ro Yeongtong Gu Suwon City Gyeonggi Do Korea 16677 Website www samsung com https partnerhub samsung com E mail airconditioner samsung com Images and data in this book...