ENGLISH-92
Optional item
Input unit
SEG1 SEG2 SEG3 SEG4
Function of the option
Remarks
Current
restriction rate
Individual
0
3
0
0
100% (Factory default)
When restriction option is
set, cooling and heating
performance may decrease.
0
1
95 %
0
2
90 %
0
3
85 %
0
4
80 %
0
5
75 %
0
6
70 %
0
7
65 %
0
8
60 %
0
9
55 %
1
0
50 %
1
1
No restriction
Oil collection
interval
Main
0
4
0
0
Factory default
0
1
Shorten the interval by 1/2
Disable
Main
0
5
0
0
Disable
This function is not applicable
for this model
0
1
Disable
Disable
Individual
0
6
0
0
Disable
This function is not applicable
for this model
0
1
Disable
Disable
Main
0
7
0
0
Disable
This function is not applicable
for this model
0
1
Disable
0
2
Disable
0
3
Disable
Setting high-
head condition
Main
0
8
0
0
Disable (Factory default)
0
1
Level 1 of height difference
type 1 (Indoor unit is lower
than outdoor unit)
When outdoor unit is over 40
~ 80 m (131’~263’) above the
indoor unit
0
2
Level 2 of height difference
type 1 (Indoor unit is lower
than outdoor unit)
When outdoor unit is over 80 m
(263’) above the indoor unit
0
3
Height difference type 2
(Outdoor unit is lower than
indoor unit)
When indoor unit is over 30 m
(98’) above the outdoor unit
Setting outdoor unit option switch and key function