Note
: MCU address and dip switch settings must be completed before Auto Pipe Pairing operation is initiated
The outdoor unit will display
E213
if addressing has not been completed
The Indoor Unit MICOM firmware version must be
“161222”
or higher see next slide
yr./month/day
To run the Auto Pipe Pairing operation, take the following steps:
1.Press the
K2
button 10 times
on the main PBA of the outdoor unit to start the Auto pipe pairing operation. (Display :
)
- The operation takes about 25 to 55 minutes normally depending on the number of indoor units connected.(Max 2hours)
Step 1 (Start
) → Steps 2 - 8 (Setup
) → Step 9 (Check
) → Step 10 (Confirmation
)
Temperature
Outdoor temp
<
75
℉
Outdoor temp 75
℉ ≥
85℉
Outdoor temp
≥
86
℉
Avg. Indoor temp
<75℉
Main heating operation
Main heating operation
Main cooling operation
Avg. Indoor temp
≥75℉
Main cooling operation
MCU Auto Pipe Pairing
Auto Addressing (H/R only)
11
Note
: Once Auto Pipe Paring has successfully completed (End)
will appear on the display. Press K3 to exit Auto Pipe Pairing..