If new dryer is installed into an existing exhaust system you must make sure:
•
The exhaust system meets all local, state, and national codes.
•
That fl exible plastic duct is not used.
•
Inspect and clean all lint buildup from inside the existing duct.
•
The duct is not kinked or crushed.
•
The exhaust hood damper opens and closes freely.
The static pressure in any exhaust system must not exceed 0.83 inches of water column, or be less than 0.
This can be measured with the dryer running with a manometer at the point where the exhaust duct connects
to the dryer. A no-heat setting should be used. The dryer tumbler shoul
REMOVE THE DOOR FROM ALL DISCARDED APPLIANCES TO AVOID THE DANGER OF A CHILD
SUFFOCATING.
LOCATION CONSIDERATIONS
The dryer should be located where there is enough space in front for loading the dryer, and enough space
behind for the exhaust system. This dryer is factory-ready for rear exhaust. To exhaust out the bottom or the
left, use the accessory exhaust kit. Instructions are included with the kit. It’s important to make sure the room
has enough fresh air. The dryer must be located where there is no air-fl ow obstruction.
On gas dryers, adequate clearance as noted on the data plate must be maintained to ensure adequate air for
combustion and proper dryer operation.
THE DRYER MUST NOT BE INSTALLED OR STORED IN AN AREA WHERE IT WILL BE EXPOSED TO
WATER AND/OR WEATHER. THE DRYER AREA IS TO BE KEPT CLEAR OF COMBUSTIBLE MATERIALS,
GASOLINE, AND OTHER FLAMMABLE VAPORS AND LIQUIDS. A DRYER PRODUCES COMBUSTIBLE
LINT. THE AREA AROUND THE DRYER SHOULD BE KEPT LINT-FREE.
ALCOVE OR CLOSET INSTALLATION
WARNING
–
The dryer must be exhausted to the outside to reduce the risk of fi re when
installed in an alcove or closet.
•
No other fuel-burning appliance should be installed in the same closet as the dryer.
•
WARNING: To reduce the risk of fi re, this dryer MUST BE EXHAUSTED TO THE OUTDOORS.
See EXHAUST INFORMATION section.
•
Minimum clearances between the dryer and adjacent walls or other surfaces are: 2” in front,
17” on top, 1” on either side, and 2.375” in the back.
•
Closet front must have two unobstructed air openings for a combined minimum total area of
72 in² with 3” minimum clearance on the top and bottom. A louvered door with equivalent space
clearance is acceptable.
Summary of Contents for DV316LG
Page 1: ...ABS Laundry Samsung Dryer Model DV316LG Maytag Technical Institute 2006 ABS L2006 002 ...
Page 2: ...Notes ...
Page 23: ...2 1 2 PRODUCT SPECIFICATIONS 2 1 THE FEATURE OF PRODUCT ...
Page 25: ...2 3 5061 RYHUYLHZ RI WKH GU HU ...
Page 31: ...3 12 Memo ...
Page 41: ...5 6 5 3 REASSEMBLY Reassembly procedures are in the reverse order of dissasembly procedures ...
Page 47: ...6 6 Memo ...
Page 52: ... 8 2 Exploded View of Front 5 2 20 11 13 6 14 1 12 11 10 15 8 16 9 7 3 4 18 19 17 10 ...
Page 57: ... 13 4 Exploded View of Frame Panel Control ...
Page 68: ...9 1 1 EORFN GLDJUDP ...
Page 69: ...9 2 Memo ...
Page 70: ...10 1 431 ZLULQJ GLDJUDP ...
Page 71: ...10 2 Memo ...
Page 75: ...11 4 Memo ...
Page 77: ...12 2 This Document can not be used without Samsung s authorization 4505 VXE SFE ...
Page 78: ...13 1 461 FLUFXLW GHVFULSWLRQV 46041 RYHUDOO V VWHP ...
Page 84: ...13 8 Memo ...
Page 85: ...14 1 471 UHIHUHQFH LQIRUPDWLRQ 47041 PRGHO QDPH ...
Page 96: ...14 12 Memo ...
Page 97: ...Notes ...