30_ Operating advanced function
Operating advanced function
fIELd SETTING ModE
field Setting value (fSv) Table
• Code 10
: Upper and lower temperature limits of each operation mode of wired remote controller
Heating(Water Out, Room), Cooling(Water Out, Room), DHW(Tank)
• Code 20
: Water law design and external room thermostat
Heating(2 WL’s for floor & FCU), Cooling(2 WL’s for floor & FCU), WL & Thermostat
types
Field Setting Value
Main Menu &
Code
Sub Menu Function
Description
Sub
Code
Default Min
Max Step Unit
Remote
Controller
Setting Range
Code 10
Water Out Temp for Cooling
Max
11
25
18
25
1
˚C
Min
12
16
5
18
1
˚C
Room Temp for Cooling
Max
21
30
24
30
1
˚C
Min
22
18
18
22
1
˚C
Water Out Temp for Heating
Max
31
55
37
55
1
˚C
Min
32
25
15
37
1
˚C
Room Temp for heating
Max
41
30
24
30
1
˚C
Min
42
16
16
22
1
˚C
DHW Tank Temp
Max
51
50
50
70
1
˚C
Min
52
40
30
40
1
˚C
Water Law
Code 20
Outdoor Temp for Water Law
(Heating)
Point
11
-10
-20
5
1
˚C
Point
12
15
10
20
1
˚C
Water Out Temp for WL1 Heating
(WL1-Floor)
Point
21
40
40
55
1
˚C
Point
22
25
17
37
1
˚C
Water Out Temp for WL2 Heating
(WL2-Fan Coil Unit)
Point
31
50
40
55
1
˚C
Point
32
35
17
37
1
˚C
Heating Water Law for Auto Mode
WL Type
41 1(WL1)
1
2(WL2)
-
-
Outdoor Temp for Water Law
(Cooling)
Point
51
30
25
35
1
˚C
Point
52
40
35
45
1
˚C
Water Out Temp for WL1 Cooling
(WL1-Floor)
Point
61
25
18
25
1
˚C
Point
62
18
5
18
1
˚C
Water Out Temp for WL2 Cooling
(WL2-Fan Coil Unit)
Point
71
18
18
25
1
˚C
Point
72
5
5
18
1
˚C
Cooling Water Law for Auto Mode
WL Type
81 1(WL1)
1
2(WL2)
-
-
External Thermostat Application
#1(Floor)
91
0(No)
0
1(Yes)
-
-
#2(FCU)
92
0(No)
0
1(Yes)
-
-