Troubleshooting
4-52
Samsung Electronics
Error Code
(cont.)
No.
Code
Description
78
E-323
Suction2 temperature sensor. (Open or Short / HR Only)
79
E-407
Compressor stop by high pressure's protection control.
80
E-410
Compressor stop by low pressure's protection control or refrigerant leakage.
81
E-413
Protection control by sump sensor.
82
E-416
Compressor stop by discharge temperature's protection control.
83
E-425
Reverse phase or phase open. ( 3φ Wiring of outdoor unit, R-S-T-N )
84
E-428
Compressor stop by abnormal compression ratio.
85
E-431
Self-diagnosis of oil solenoid valve. ( Open and Close error ) or closing error of oil balance valve.
86
E-438
EVI EEV leakage or intercooler leakage.
87
E-439
Refrigerant leakage.
88
E-440
Prohibition of heating operation when the ambient temperature is over 30°C
89
E-442
Prohibition of refrigerant charging with heating operation when outdoor ambient temperature is over 15°C
90
E-443
Prohibition of operating when the high pressure of system is too low.
91
E-445
CCH wire is broken or Sump sensor detached from the position.
92
E-452
Power failure temporarily or zero crossing error.
93
E-453
Overload error of outdoor unit's fan motor. ( by temperature )
94
E-454
RPM error of outdoor unit's fan motor.
95
E-455
IPM overload error of outdoor unit's fan motor. (by temperature)
96
E-457
Backlash error of outdoor unit's fan motor.
97
E-458
Over current of CT sensor.
98
E-461
Low current of CT sensor.
99
E-477
Stop compressor, because liquid refrigerant get into the compressor.
100
E-559
Indoor unit stop by unidentified error from outdoor units.
101
E-560
Option switch setting error of outdoor unit. ( Inapplicable option switch turns on. )
102
E-561
Fan RPM error of ERV SA. (Supply air)
103
E-562
Fan RPM error of ERV RA. (Return air)
104
E-563
Model mismatching of Indoor unit.
105
E-601
Communication error between remote controller and indoor unit.
106
E-602
Communication error between master and slave wired remote controller.
107
E-603
Communication packet error. (Baud rate error)
108
E-604
Tracking failure error between wired remote controller and indoor unit.
109
E-605
Communication error. ( 7-day scheduler
l
Wired remote controller or 7-day scheduler
l
Centralized controller )
110
E-606
COM1/COM2 communication setting error. ( Wired remote controller )
111
E-607
Two masters of wired remote controllers were installed in one COM2 communication line.
112
E-608
Can't detect ERV controller.
113
E-609
Indoor unit is not detected for synchronous control.
114
E-610
Communication error between centralized controller and interface module.
115
E-611
Communication error between DMS and centralized controller.
116
E-613
Communication error between DMS and SIM interface module.
117
E-614
Communication error between SIM and power meter.
118
E-615
Communication error between interface module and indoor unit.
$9;&6+B$BaLQGG
Summary of Contents for AVXC2H056EE
Page 91: ...3 43 Samsung Electronics MEMO 9 6 B B a LQGG ...
Page 227: ...MEMO Samsung Electronics 4 136 9 6 B B a LQGG ...
Page 243: ...MEMO Samsung Electronics 5 16 9 6 B B a LQGG ...
Page 247: ...MEMO Samsung Electronics 5 20 9 6 B B a LQGG ...
Page 279: ...MEMO Samsung Electronics 5 52 9 6 B B a LQGG ...
Page 292: ...Exploded Views and Parts List 5 65 Samsung Electronics ND045 056 071QHXE 9 6 B B a LQGG ...
Page 297: ...MEMO Samsung Electronics 5 70 9 6 B B a LQGG ...
Page 359: ...MEMO Samsung Electronics 6 12 9 6 B B a LQGG ...
Page 365: ...MEMO Samsung Electronics 6 18 9 6 B B a LQGG ...
Page 373: ...MEMO Samsung Electronics 6 26 9 6 B B a LQGG ...
Page 377: ...MEMO Samsung Electronics 6 30 9 6 B B a LQGG ...
Page 381: ...MEMO Samsung Electronics 6 34 9 6 B B a LQGG ...
Page 385: ...MEMO Samsung Electronics 6 38 9 6 B B a LQGG ...
Page 389: ...MEMO Samsung Electronics 6 42 9 6 B B a LQGG ...