Operating Instructions and Installation
3-9
Samsung Electronics
No.
JOB
EXPLANATION
PRECAUTIONS
1
Determine the
• Suitable location
• Avoid sandy or gravelly soil as its grounding
grounding position.
a) Place that is always dank.
resistance is high.
b) Hard soil rather than loose sandy soil.
• The grounding wire for the telephone line cannot
be used for the grounding of the air conditioner.
• Unsuitable location
• When the grounding electrode is to be installed
a) Where there are underground structures or
under a place with heavy traffic, its wire must be
facilites such as gas pipes, water pipes,
connected firmly with the utmost care.
telephone lines, underground cables, etc.
b) A place 2m or less from the lightning arrester
grounding electrode and its cable.
2
Drive the grounding
a) Dig a hole to the size illustrated,
electrode into position.
and drive in the grounding electrode.
b) Cover the top of the grounding
electrode with excavated soil.
3
Put the grounding
a) If the grounding wire is too short, connect an
• The grounding wire should be a green
wire in order.
extention lead to it. Solder the joint and
insulated wire of ø1.6mm or 2mm
2
or larger.
wrap it with tape.
• The soldered joint should not be buried
b) Fasten the grounding wire with staples.
underground.
4
Check the
a) After grounding work, measure the grounding
workmanship,
resistance with a grounding resistance tester.
and provide
corrective
b) If the resistance is above a specified level,
measures if
drive the grounding electrode in deeper
necessary.
or increase the number of grounding
electrodes.
5
Connect the
Secure the grounding wire to the
grounding
grounding terminal of the air conditioner
wire to the air
conditioner.
3-2-2(f) Grounding
(The Parts for this work are optional.)
• A g rounding terminal can be found on
the outdoor unit as illustrated.
1. When an existing grounding terminal is avilable.
( G rounding wire of ø1.6mm or larger<solid w i re > o r
2 m m
2
or larger <standard wire > )
2. Use of a grounding electro d e .
• Specifications of grounding electro d e .
Terminal used exclusively
for grounding.
Steel core
Carbon plastic
PVC-Insulated(2mm
2
x3.5m), green
Terminal, M4
Grounding resistance ;
Less than 100 ohms
(existing grounding electrode)
Summary of Contents for AS180UE
Page 2: ...Samsung Electronics Co Ltd FEB 1999 Printed in Korea Code No DB81 10161A 3...
Page 4: ...1 2 Samsung Electronics MEMO...
Page 20: ...3 14 Samsung Electronics MEMO...
Page 34: ...Samsung Electronics 6 1 6 Exploded Views and Parts List 6 1 Indoor Unit...
Page 40: ...6 7 Samsung Electronics MEMO...
Page 41: ...Samsung Electronics 6 1 6 Exploded Views and Parts List 6 1 Indoor Unit...
Page 47: ...6 7 Samsung Electronics MEMO...
Page 50: ...Samsung Electronics 7 3 MEMO...
Page 54: ...Samsung Electronics 10 1 10 Schematic Diagrams 10 1 Indoor Unit...