6-2-9 Overload protection control
●
AT HEATING MODE
◆
If indoor heat exchanger temp. is over 53°C, outdoor fan turns off.
◆
If indoor heat exchanger temp. is over 60°C, outdoor compressor stops and Indoor fan speed is low.
◆
The indoor fan, outdoor fan and compressor will resume normal operation when the indoor heat exchanger temperature drops
below 50˚C.
Indoor Heat Exchanger Temp.
60˚C + offset
53˚C + offset
50˚C + offset
Compressor
Outdoor Fan
Indoor Fan
ON
ON
Time
ON
OFF
OFF
Low Speed
3min Delay
2Sec
ON
Setting Speed
*offset = 0, 1, 2, 3˚C