Performing Leak Tests
Placing the Indoor Unit in Position
C
OMPLETING THE
I
NSTALLATION
E-
13
ENGLISH
Once you have checked that there are no leaks in the system, you can insulate
the piping, hose and cables and place the indoor unit on the installation plate.
1
To avoid condensation problems, place heat-resistant polyethylene foam
separately around each refrigerant pipe in the lower part of the indoor unit.
2
Wrap the refrigerant pipes and the drain hose located at the rear of the
indoor unit up in the absorbent pad.
➢
Triply wind the pipes and hose to the end of the indoor unit with
the absorbent pad (make intervals of 20mm).
3
Wind insulating tape around the pipes, assembly cable and drain hose.
4
Place the resulting bundle carefully in the lower part of the indoor unit,
making sure that it does not jut out from the rear of the indoor unit.
5
Hook the indoor unit on to the installation plate and move the unit to the right
and left until you are sure that it is securely in place.
6
Finish wrapping vinyl tape around the rest of the piping leading to the
outdoor unit.
7
Using clamps (optionally supplied), attach the piping to the wall wherever
possible.
Installation plate
Before completing the installation (insulation of the cables, hose and
piping and fixing of the indoor unit to the installation plate), you must
check that there are no gas leaks.
To check for gas leaks on the...
Then, using a leak detector,
check the...
Indoor unit
Flare nuts at the end of sections
C and D.
Outdoor unit
Valves on sections A and B.
C
D
A
B
❊
The designs and shape are subject to
change according to the model.