118
SAMSUNG ELECTRONICS
12-5 Installation
12-5-1 Before Installation
Keep the air conditioner outlet and inlet free from its surroundings.
In case of installation, keep the symmetry and fix it to prevent vibration.
The pipe length shall meet the standard as far as possible.
12-5-2 Installation Procedure
■
Location
Install the product in an area to guarantee the best cooling effect, convenience of piping and electric work, and inexistence of
vibration or wind.
■
Wall Drilling
Drill the wall downward in a diameter of 60 to 65mm.
■
Fixing Indoor Unit & Outdoor Unit
Fix the air conditioner indoor unit securely to the wall. Secure the outdoor unit in a suitable position.
■
Pipe Spooling & Connectingt
You shall cut the pipe with a pipe cutter and grind all the burrs of the cut surface. pipe expansion may continue until the pipe
surface becomes uneven or torn apart. Be sure to use a torque wrench to tighten pipes or flare nuts.
■
Leak Test
Put an inset gas like nitrogen in the outdoor unit pipe and put soap bubbles or other test liquids on the pipe surface for the leak
test.
■
Drain Hose Connecting
I
nstall the drain hose downward to drain water naturally. Be sure to pour water into the hose to check if it drains well.
■
Electric & Earth Work
Electric and earth work shall meet the "Electric Facility Technology Standard" and the "Internal Wire Regulation" of the Electric
Business Laws.
■
Inspection & Trial Run
Upon completion of the tests, you shall make a trial run while you explain the main functions of the air conditioner to finish the
installation.
<Torque & Depth>
Outer Diameter (D)
Torque(kgf·cm)
Depth(A)
ø6.35 mm(1/4")
140~170
1.3 mm
ø9.52 mm(3/8")
250~280
1.8 mm
ø12.70 mm(1/2")
380~420
2.0 mm
ø15.88 mm(5/8")
440~480
2.2 mm
ø19.05 mm(4/4")
9900~1,210
2.2 mm
Pipe
Flare
Summary of Contents for AR09TXFCAWKNEU
Page 78: ...77 SAMSUNG ELECTRONICS 7 Wiring Diagram 7 1 Indoor Unit CODE DB68 08680A 01 ...
Page 80: ...79 SAMSUNG ELECTRONICS 8 PCB Diagram 8 1 Indoor Main PCB DB92 04839A ...
Page 81: ...80 SAMSUNG ELECTRONICS 8 2 Outdoor PCB DB92 04837A ...
Page 82: ...81 SAMSUNG ELECTRONICS ...
Page 84: ...83 SAMSUNG ELECTRONICS 8 4 DISPLAY PCB DB92 04833B ...
Page 107: ...106 SAMSUNG ELECTRONICS 11 Block Diagram 11 1 Indoor unit ...
Page 108: ...107 SAMSUNG ELECTRONICS 11 2 Outdoor unit ...
Page 118: ...117 SAMSUNG ELECTRONICS ...