89
10-2-11 Compressor wire missing error/rotation error
Indoor display
3-LED DISPLAY
7-SEG DISPLAY
DESCRIPTION
LED1
LED2
LED3
◎
◎
E467
Compressor wire missing errorr/rotation error
Outdoor display
●
●
Compressor wire missing error/rotation error
●
LED ON
◎
LED BLINKING
LED OFF
1. Checklist :
1) Is the connection of cable for the compressor?
2) Is the compressor wire is connected clockwise? U(RED)-V(BLU)-W(YEL)
3) Is the interphase resistance of compressor normal?
2. Troubleshooting procedure
NO
NO
NO
NO
YES
YES
YES
YES
Restart after power off.
Is the restart error occurred again?
Is the connection of
compressor wire is normal?
(PBA and Compressor)
Is the restart error occurred again?
Is the compressor body and
interphase resistance insulated?
Exchange the compressor
Exchange the Outdoor PBA
Terminate the service
Connect the comp wire normally
Terminate the service