10-
Samsung Electronics
㽞
New Function [ Indoor Terminal Block Safety Device ]
1. Thermal Fuse is installed in Terminal Block as below.
(Thermal Fuse is used to prevent PL caused by a defective connection of indoor and outdoor units)
T
hermal
Fu
se
Terminal Block Internals
Connection of terminal block
and Main PBA
2. Thermal Fuse is opened when internal temperature of Terminal Block goes to a certain point due to Tracking caused by
a defective connection of indoor and outdoor units.
- When Thermal Fuse is opened, Main PBA (DC12V) is turned off and the indoor unit does not operate.
(There is no problem with Main PBA in this case)
- In the above case, the change of all-in-one Terminal Block will make Main PBA operate again.
Circuit Block
3. Measurement method of fair/defective thermal fuse
Fail
Defective
Summary of Contents for AR09KSWSPWKNCV
Page 38: ...4 2 Outdoor Unit 5 6 9 3 Detach the Cabinet Upper li e the picture...
Page 40: ...8 4 9 4 20...
Page 41: ...4 21...
Page 43: ...4 Samsung El ectronics 2 2 _AR18K6 3 4 9...
Page 91: ...SamsungEle ctr onic s 7 1 7 Wiring Diagram 7 1 Indoor Unit_AR09 12KSWSPWKNCV DB68 04014A 5...
Page 92: ...DB68 05092A 3 AR09 12 18 24KSFPDWQNCV 7 2 Samsung Electronics...
Page 93: ...7 Samsung Electronics 7 2 Outdoor Unit...
Page 150: ......