Samsung AQV36W Installation Manual Download Page 10

E-

9

ENGLISH

I

NSTALLING

 

THE

 A

IR

 

CONDTIONER

Installing and Connecting the Drain Hose of the Indoor Unit

When installing the drain hose for the indoor unit, you should check if condensate draining is adequate.  
When you pass the drain hose through the 65mm hole drilled in the wall, check the following. 

To install the drain hose, do the following.

1

If necessary, connect the 6.6ft(2m) extension drain hose to the drain hose. 

2

If you use the extension drain hose, insulate the inside of the extension drain 

hose with a shield.

3

Fit the drain hose into 1 of 2 drain hose holes, and then fix the end of the  

drain hose with a clamp tightly. 

  If you don’t use the other drain hose hole, block it with a rubber stopper. 

4

Pass the drain hose under the refrigerant pipe keeping the drain hose tight. 

5

Pass the drain hose through the hole in the wall. Check if it slants downwards 

as seen in the picture. 

The hose will be fixed permanently into position after finishing the 
installation and the gas leak test; refer to page 12 for further details. 

Installing and Connecting the Drain Hose of the Outdoor Unit

While heating, ice may accumulate. During the process of defrosting, you 
should check if condensate draining is adequate.  
For the adequate draining, do the following.

1

Insert the drain plug into the drain hole on the underside of the outdoor 

unit.

2

Connect the drain hose to the drain plug.

3

Ensure that condensate draining is adequate.

Shield

Drain hose

Extension drain hose

Drain hole

The hose must  

 NOT slant upwards. 

The end of the drain 

hose must NOT be 

placed under water. 

Do NOT bend the hose 

in different directions.

Keep a clearance of 

at least 2inch(50mm)   

between the end 

of the hose and the 

ground.

2inch

(50mm)

less

Do NOT place the end 

of the drain hose in a 

hollow.

Ditch

Summary of Contents for AQV36W

Page 1: ...ENGLISH Split type Air Conditioner Cooling and Heating INSTALLATION MANUAL AQV36W E DB98 29387A 1 S F ESPAÑOL FRANÇAIS ...

Page 2: ...E 1 ENGLISH P ...

Page 3: ... window type air conditioner The manufacturer is not responsible for the accidents or injury caused by an incorrect installation When installing the built in type air conditioner keep all electric cables such as the power cable and the connection cord in pipes ducts or cable channels to protect them from the danger of impact or any other incidents INSTALLING THE AIR CONDITIONER If the power cord o...

Page 4: ...ecting the Drain Hose of the Indoor Unit 9 Installing and Connecting the Drain Hose of the Outdoor Unit 9 Installing and Connecting the Assembly Pipe of the Indoor Unit 10 Cutting or Extending the Pipe 11 COMPLETING THE INSTALLATION Purging the Connected Pipes 12 Performing the Gas Leak Tests 13 Fixing the Indoor Unit in Place 13 Fixing the Outdoor Unit in Place 14 Final Checks and Trial Operation...

Page 5: ...r lubricating oil may run into the circuit and damage the outdoor unit seriously Choose a dry and sunny place avoiding direct sunlight or strong winds Do not obstruct the passage Avoid a place that may disturb your neighbor A noise may occur from the outdoor unit and the discharged air may run into the neighborhood Choose a place where you can easily connect the pipes and cables to the indoor unit...

Page 6: ...2ft 15m maximum 23 6inch 600mm minimum 11 8inch 300mm minimum 98 4ft 30m maximum 11 8inch 300mm minimum 23 6inch 600mm minimum 4 9inch 125mm or more Wrap the refrigerant pipes and the drain hose with the absorbent pad and vinyl tape Refer to page 13 for further details 4 9inch 125mm or more PREPARING THE INSTALLATION The appearance of the unit may be different from the diagram depending on the mod...

Page 7: ...ner is supplied without the assembly pipe as seen in the picture below If these accessories are supplied you can find them in the accessory box Accessories in the Outdoor Unit Case Accessories in the Indoor Unit Case Installation Plate 1 Remote Control 1 Batteries for Remote Control 2 User s Manual 1 Installation Manual 1 3 wire Power Cable 1 2 wire Assembly Cable 1 5 wire Assembly Cable 1 The fol...

Page 8: ...or bolts must not be projected by more than 0 8inch 20mm 4 Determine the positions of the wooden uprights to be attached to the window frame 5 Attach the wooden uprights to the window frame giving attention to the weight of the indoor unit 6 Attach the installation plate to the wooden uprights using tapping screws as seen in the picture Purging the Indoor Unit On delivery there may be inert gas in...

Page 9: ...rew carefully 7 Close the front grille 8 Remove the terminal board cover on the side of the outdoor unit 9 Connect the cables to the terminals as seen in the picture Each wire is labeled with the corresponding terminal number 10 Connect the earth conductor to the earth terminals 11 Close the terminal board cover tightening the screw carefully 12 Connect the power cable to the indoor unit Connectin...

Page 10: ... 5 Pass the drain hose through the hole in the wall Check if it slants downwards as seen in the picture The hose will be fixed permanently into position after finishing the installation and the gas leak test refer to page 12 for further details Installing and Connecting the Drain Hose of the Outdoor Unit While heating ice may accumulate During the process of defrosting you should check if condensa...

Page 11: ...ds and then with a torque wrench applying the following torque Outer Diameter D Torque 1 4 inch 6 35mm 10 1 12 3 ft lb 140 170 kgh cm 3 8 inch 9 52mm 18 1 20 3 ft lb 250 280 kgh cm 5 8 inch 15 88mm 31 8 34 7 ft lb 440 480 kgh cm 3 4 inch 19 05mm 71 6 87 5 ft lb 990 1210 kgh cm If you want to shorten or extend pipes refer to page 11 4 Cut off the remaining foam insulation 5 If necessary bend the pi...

Page 12: ...s at the cut edge of the pipe using a reamer 4 Put a flare nut slightly into the pipe and modify the flare Outer Diameter D Depth A 1 4 inch 6 35mm 0 05 inch 1 3mm 3 8 inch 9 52mm 0 07 inch 1 8mm 5 8 inch 15 88mm 0 09 inch 2 2mm 3 4 inch 19 05mm 0 09 inch 2 2mm 5 Check if you flared the pipe correctly There are some examples of incorrectly flared pipes below 6 Align the pipes to connect them easil...

Page 13: ...picture 4 Open the valve of the low pressure side of manifold gauge counterclockwise 5 Purge the air in the connected pipes using vacuum pump for about 10 minutes Close the valve of the low pressure side of manifold gauge clockwise Make sure that pressure gauge show 0 1MPa 76cmHg after about 10 minutes This procedure is very important to avoid a gas leak Turn off the vacuum pump Remove the hose of...

Page 14: ...stallation plate 1 To avoid condensation problems place heat resistant polyethylene foam separately around each refrigerant pipe in the lower part of the indoor unit 2 Wrap the refrigerant pipe and the drain hose in the rear of the indoor unit with the absorbent pad Wind the pipe and hose three times to the end of the indoor unit with the absorbent pad 0 79inch 20mm interval 3 Wind the pipe assemb...

Page 15: ... noise and vibration Fixing the Outdoor Unit in Place X mm Rubber leg Y mm Final Checks andTrial Operation To complete the installation perform the following checks and tests to ensure that the air conditioner operates correctly 1 Check the following Strength of the installation site Tightness of pipe connection to detect a gas leak Electric wiring connection Heat resistant insulation of the pipe ...

Page 16: ...rt and stop the air conditioner 2 How to select the modes and functions 3 How to adjust the temperature and fan speed 4 How to adjust the airflow direction 5 How to set the timers 6 How to clean and replace the filters When you complete the installation successfully hand over the User s Manual and this Installation Manual to the user for storage in a handy and safe place Providing Information for ...

Page 17: ...Printed in Korea ...

Reviews: