5-2-3 When the Outdoor Unit Does Not Operate. (Initial Diagnosis)
1 )
Checklist :
(1) Is input voltage normal? (the rating voltage
±
10% range)
(2) Is the set temperature of the remote control higher than room temperature in COOL m o d e ?
(3) Is the set temperature of the remote control lower than room temperature in HEAT mode?
(4) Is the POWER IN connector (CN78) linked corre c t l y ?
(5) Is the outdoor unit properly connected with the TERMINAL BLOCK connector(7P)?
2 )
Troubleshooting pro c e d u re
Troubleshooting
After unplugging out the power cord should be recon-
nected within five seconds.
Does the operating lamp blink
YES
YES
NO
NO
NO
NO
NO
YES
NO
Outdoor unit is
out of order.
Power relay is
out of order
Power relay should be
replaced.
PCB should be
checked.
PCB is
out of order.
PCB and Room tempera-
ture sensor should be
checked.
Room temperature sensor is
out of order
Check as in the procedure "No Power parts"
Refer to page 5-2.
YES
②
②
①
①
①
➂
➂
Is the room sensor normal register?
(25°C
→
10K
Ω
)
10°C
20°C
30°C
17.96k
Ω
12.09k
Ω
8.3k
Ω
Does the timer lamp blink during operation ?
Is the power relay RY71 operated by adjusting the room
temperature?
Is the rating voltage ±10% range applied relay between
CN78
①
and
➂
.
Test rod location
Normal
+ - Condition
Voltage
IC04 Pin #59 GND RY71 ON DC 4.8V
Summary of Contents for AQT24A1QE/B
Page 2: ...Samsung Electronics Co Ltd DEC 1998 Printed in Korea Code No DB81 00029A 1...
Page 4: ...1 2 Samsung Electronics MEMO...
Page 9: ...2 5 Samsung Electronics 2 4 Pressure Graph 24K BTU 18K BTU...
Page 10: ...2 6 Samsung Electronics MEMO...
Page 28: ...4 5 Samsung Electronics MEMO...
Page 38: ...Samsung Electronics 6 1 6 Exploded Views and Parts List 6 1 Indoor Unit...
Page 46: ...6 9 Samsung Electronics MEMO...
Page 48: ...Samsung Electronics 8 1 8 PCB Diagrams 8 1 Main PCB B B B...
Page 51: ...Samsung Electronics 9 1 9 Wiring Diagrams 9 1 Indoor Unit...
Page 54: ...Samsung Electronics 10 1 10 Schematic Diagrams 10 1 Indoor Unit PNA4612MOOXD...