5-2-3 When the Outdoor Unit Does Not Operate. (Initial Diagnosis)
1)
Checklist :
(1) Is input voltage normal?
(2) Is the set temperature of the remote control higher than room temperature in COOL mode?
(3) Is the POWER IN connector (CN71) linked correctly?
(4) Is the outdoor unit properly connected with the TERMINAL BLOCK connector((N1), 1)?
2)
Troubleshooting procedure
Troubleshooting
After unplugging out the power cord should be
reconnected within five seconds.
Does the STD lamp blink
YES
YES
NO
NO
NO
NO
YES
YES
Outdoor unit is
out of order.
Power relay is
out of order
Power relay should be
replaced.
PCB should be
checked.
Microcomputer is
out of order.
PCB should be checked.
Room temperature sensor is
out of order
Check as in the procedure "No Power parts"
Refer to page 5-2.
Is the room sensor normal register?
10°C
20°C
30°C
17.96k
Ω
12.09k
Ω
8.3k
Ω
Does the timer lamp blink during operation ?
Is the power relay RY71 operated by adjusting the room
temperature?
Is rating voltage ±10% range applied relay between Terminal block
NO(N1) and No. 1
Test rod location
Normal
+ - Condition
Voltage
IC4 Pin No.62 GND RY71 ON DC 4.8V
3
1
1
2
3
2
NO
YES
00181_TSHOO_9 11/6/00 5:17 PM Page 5-4
Summary of Contents for AQ12A5(6)MB
Page 2: ...ELECTRONICS Samsung Electronics Co Ltd Sep 2000 Printed in Korea Code No DB81 00181A 2...
Page 4: ...1 2 Samsung Electronics MEMO...
Page 9: ...3 4 Samsung Electronics MEMO...
Page 30: ...Samsung Electronics 5 13 MEMO...
Page 33: ...Samsung Electronics 6 3 6 2 Outdoor Unit UQ12A5 6 MB E...
Page 42: ...Samsung Electronics 8 1 8 PCB Diagrams 8 1 ASS Y MAIN PCB DB93 00267A TOP PATTERN...
Page 44: ...Samsung Electronics 8 3 8 2 ASS Y MAIN PCB DB93 00267A BOTTOM PATTERN...
Page 47: ...Samsung Electronics 9 1 9 Wiring Diagrams 9 1 Indoor Unit...
Page 50: ...10 1 Indoor Unit Samsung Electronics 10 1 10 Schematic Diagrams...