35

3.  Connect the charging hose of the low-pressure side of manifold gauge to a 

gas service port as seen in the picture.

4.  Open the valve of the low pressure side of manifold gauge counterclockwise.

5.  Purge the air in the connected pipes using the vacuum pump for about  

15 minutes. 

  

   Make sure that pressure gauge shows -0.1MPa(-76cmHg) after about 

10 minutes.  

This procedure is very important to avoid a gas leak. 

  

   Close the valve of the low pressure side of manifold gauge clockwise. 

  

   Turn off the vacuum pump. 

  

   Check for 2 minutes if there is any pressure change.

  

   Remove the hose of the low pressure side of manifold gauge.

6.  Set a valve cork of liquid and gas service port to the open position.

7.  Mount the valve stem nuts and the service port cap to the valve, and tighten 

them at the torque of 183kgf•cm with a torque wrench.

8.  Check for a gas leak paying particular attention to the 3-way valve’s stem nuts 

and to the service port cap (Refer to page 37).

Vacuum 

Pump

Manifold gauge

Valve

Gas service port 

<Low pressure> 

Liquid service port 

<High pressure> 

(Backward flowing 

prevention)

•   The remaining air in the Refrigeration cycle, which contains moisture, may cause malfunction on the compressor.
•   Always contact the service center or a professional installation agency for product installation.

B

(liquid)

Stem nut

Valve stem

A

(Gas)

Add refrigerant charge according to table below: 

If you use a pipe longer than 5m,

‘A’g of refrigerant R410A must be added for each extra meter.

If you use a pipe shorter than 5m,

The purge time is normal.

Refer to the Service Manual for further details.

Adding Refrigerant

Model

A



09



10



12



20



18



20



24



25

Boracay EUR_AQ09T&U@_IBIM_32447A_E.indd   35

2011-3-19   10:08:20

Summary of Contents for AQ09UGFN

Page 1: ...Boracay EUR_AQ09T U _IBIM_32447A_E indd 1 2011 3 19 10 07 24...

Page 2: ...ries 26 Fixing the installation plate 27 Connecting the assembly cable 28 Installing and connecting the assembly pipe of the indoor unit 30 Purging the indoor unit 31 Cutting or extending the pipe 31...

Page 3: ...tric shock or fire Fix the outdoor unit firmly so that the electric part of the outdoor unit is not exposed Failing to do so may result in electric shock or fire Do not install this appliance near a h...

Page 4: ...a gas leak such as propane gas LP gas etc ventilate immediately without touching the power plug Do not touch the appliance or power cord Do not use a ventilating fan A spark may result in an explosion...

Page 5: ...hock fire or problems with the product Do not drink the water from the air conditioner The water may be harmful to humans Do not apply a strong impact to the remote controller and do not disassemble t...

Page 6: ...ction operates if an internal fault occurs in the air conditioner Type Description Against cold air The internal fan will be off to against cold air when the heat pump is heating De ice cycle The inte...

Page 7: ...n Blade pin lever Air intake Air flow blade left and right Air filter underthepanel Air intake Room temperature sensor 09 12 18 24T 09 12 18 24U Air filter underthepanel Air flow blade up and down Bla...

Page 8: ...ferent fan speeds such as Auto Low Medium High Set Set the timer mode Cancel Cancel the timer mode Air swing Activate Deactivate air flow blade movement automatically up and down Mode Set one of the 5...

Page 9: ...tes on the rear side of the remote controller and pull up 2 Insert two AAA batteries Check and match the and signs accordingly Make sure you have inserted the batteries in correct position 3 Close the...

Page 10: ...rature and the fan speed to feel cooler in hot season If current outside temperatures are much higher than the selected indoor temperature it may take time to bring the inner temperature to the desire...

Page 11: ...s the button to adjust the temperature Auto You can adjust the desired temperature by 1 C within the range of 16 C 30 C Cool You can adjust the desired temperature by 1 C within the range of 16 C 30 C...

Page 12: ...button on the remote controller during Cool mode Turbo indicator appears on the remote controller display and the air conditioner operates inTurbo function for 30 minutes Move the blade pin lever left...

Page 13: ...nd T U indicator on the indoor unit Set Off timer in mode over 5 hours You fell disturbed sleep if the is set too short or long because the default is set to 8 hour operation If the mode is set less t...

Page 14: ...icator stops blinking and reserved time will be displayed for 3 seconds If you don t press Set button within 10 seconds after selecting the time the air conditioner will return to previous status Chec...

Page 15: ...l set the temperature range limit to help you save energy while the air conditioner is operating in Cool mode Press the SmartSaver button on the remote controller while the air conditioner is operatin...

Page 16: ...operation Whentheairconditioneristurnedoff The Auto clean indicator on the indoor unit display appears and the Auto cleaning function runs Whentheairconditioneristurnedon After stopping the air condit...

Page 17: ...acid hydrochloric acid organic solvents such as thinner kerosene and acetone etc to clean the surface of the product or put any stickers on it They may damage the surface of the air conditioner Be car...

Page 18: ...Air filter in a ventilated area Clean the Air filter with a vacuum cleaner or soft brush If dust is too heavy rinse it with running water Clean the Air filter every 2 weeks or when the filter clean r...

Page 19: ...1 Clean the condensate drain pan 2 Thoroughly clean the heat exchanger 2 Clean the condensate drain pipe 2 Replace the remote controller batteries 1 Outdoor unit Clean the heat exchanger on the outsid...

Page 20: ...r does not come out If the doors or windows are open it may cause bad cooling heating performance Close the doors and windows Check if the air conditioner has just been turned on after stopping coolin...

Page 21: ...refrigerant flow movement changes It is normal Smoke is generated from the outdoor unit If may not be a fire but it can be a steam generated by the defrost operation from outdoor heat exchanger during...

Page 22: ...ly for the applications for which it has been designed the indoor unit is not suitable to be installed in areas used for laundry Do not use the units if damaged If problems occur switch the unit off a...

Page 23: ...scaffolding or any other means of elevation won t be considered in warranty and charged to end user Power supply line fuse or circuit breaker Always make sure that the power supply is compliant with c...

Page 24: ...picture below when installing the air conditioner Avoid the following places to prevent malfunction of the unit Where there is machine oil Salty environment such as seaside areas Where sulfide gas exi...

Page 25: ...d the air outlet is towards the wall 500 or more 300 or more The upper part of the outdoor unit and the air outlet is opposite the wall When the walls are blocking front and the rear side of the outdo...

Page 26: ...will not cause any effect Accessories The following accessories are supplied with the air conditioner The number of each accessory is indicated in parentheses Accessories in the indoor unit case Acce...

Page 27: ...Finder TorqueWrench Pipe Cutter Reamer Pipe Bender Spirit Level Screw Driver Spanner Drill LWrench MeasuringTape Tools for test operations Thermometer Resistance Meter Electroscope You can select the...

Page 28: ...essary Do not connect two or more different cables to extend the length It may cause fire Make sure that a wall can withstand the weight of the product If you install the product in a place where it i...

Page 29: ...ellow Ground wire Green Yellow Indoor unit Outdoor unit Ground wire Green Yellow Ground wire Green Yellow End of the wire must be circular After connecting the cables make sure terminal numbers on the...

Page 30: ...ressures of at least 4200 kPa and for burst pressure of at least 20700 kPa Under no circumstances must sanitary type copper pipe be used There are 2 refrigerant pipes of different diameters The smalle...

Page 31: ...e length of the pipe can be Extended up to see table page 24 Shorten up to see page 24 If you need a pipe longer than 5 meters You must extend the assembly cable You must add refrigerant to the pipes...

Page 32: ...first with your hands and then with a torque wrench applying the following torque 7 For further details on how to connect to the outdoor unit and purge the air refer to page 34 36 Correct Uneven Thic...

Page 33: ...and turning to the left 3 Insert the drain hose by fixing it with the screw into the groove of the drain hose and the outlet of the drain pan 4 Attach the rubber cap with a screwdriver by turning it t...

Page 34: ...plug 3 Ensure that condensation draining is adequate Drain hole Drain plug To avoid drain plug from contacting the ground secure gap between the ground and the bottom surface of the outdoor unit In ar...

Page 35: ...cap to the valve and tighten them at the torque of 183kgf cm with a torque wrench 8 Check for a gas leak paying particular attention to the 3 way valve s stem nuts and to the service port cap Refer t...

Page 36: ...harge the refrigerant Important information regulation regarding the refrigerant used Charging the refrigerant under conditions of liquid by using a liquid pipe a Factory refrigerant charge of the pro...

Page 37: ...alves discharge all the nitrogen from the system and create vacuum according to page 34 36 After opening valves check leaks using a leak detector for refrigerant Pump down before disconnecting the ref...

Page 38: ...ce the outdoor unit as indicated on the top of the unit to let the discharged air out properly 2 Fix the outdoor unit in level to an appropriate support using anchor bolts 3 If the outdoor unit is exp...

Page 39: ...f the air conditioner 6 Disconnect the pipes 3 Press the Airswing button and check the following The airflow blades work properly 4 Press the Power button to stop the operation 2 Press the Mode button...

Page 40: ...insulation tape twice and position your contraction tube in the middle of the insulation tape 5 Apply heat to the contraction tube to contract it 6 After tube contraction work is completed wrap it wi...

Page 41: ...ENGLISH 41 Memo Boracay EUR_AQ09T U _IBIM_32447A_E indd 41 2011 3 19 10 08 25...

Page 42: ...amsung com KOSOVO 381 0113216899 LUXEMBURG 261 03 710 www samsung com MACEDONIA 023 207 777 MONTENEGRO 020 405 888 NETHERLANDS 0900 SAMSUNG 0900 7267864 0 10 Min www samsung com NORWAY 815 56 480 www...

Page 43: ...DB98 32447A 1 Air Conditioner user installation manual imagine the possibilities Thank you for purchasing this Samsung product To receive more complete service please register your product at www sams...

Reviews: