7
1. Combination Table: Outdoor units
Premium Compact
System Model
Capacity of Single Unit (HP)
Capa
Code
No. of Modules
8HP 10HP 12HP 14HP 16HP 18HP 20HP 22HP 24HP 26HP 28HP 30HP
8HP AM080JXVHGH/EU
1
1
10HP AM100JXVHGH/EU
1
1
12HP AM120JXVHGH/EU
1
1
14HP AM140KXVGGH/EU
1
1
16HP AM160KXVGGH/EU
1
1
18HP AM180KXVGGH/EU
1
1
20HP AM200KXVGGH/EU
1
1
22HP AM220KXVGGH/EU
1
1
24HP AM240KXVGGH/EU
1
1
26HP AM260KXVGGH/EU
1
1
28HP AM280KXVGGH/EU
1
1
30HP AM300KXVAGH/EU
1
1
32HP AM320KXVGGH1EU
2
1
1
34HP AM340KXVGGH1EU
2
1
1
36HP AM360KXVGGH1EU
2
1
1
38HP AM380KXVGGH1EU
2
1
1
40HP AM400KXVGGH1EU
2
1
1
42HP AM420KXVGGH1EU
2
1
1
44HP AM440KXVGGH1EU
2
1
1
46HP AM460KXVGGH1EU
2
1
1
48HP AM480KXVGGH1EU
2
1
1
50HP AM500KXVGGH1EU
2
1
1
52HP AM520KXVGGH1EU
2
1
1
54HP AM540KXVGGH1EU
2
1
1
56HP AM560KXVGGH1EU
2
1
1
58HP AM580KXVGGH1EU
2
1
1
60HP AM600KXVGGH1EU
2
2
62HP AM620KXVGGH1EU
3
1
1
1
64HP AM640KXVGGH1EU
3
1
1
1
66HP AM660KXVGGH1EU
3
1
1
1
68HP AM680KXVGGH1EU
3
1
1
1
70HP AM700KXVGGH1EU
3
1
1
1
72HP AM720KXVGGH1EU
3
1
1
1
74HP AM740KXVGGH1EU
3
2
1
76HP AM760KXVGGH1EU
3
1
1
1
78HP AM780KXVGGH1EU
3
1
1
1
80HP AM800KXVGGH1EU
3
1
1
1
82HP AM820KXVGGH1EU
3
1
2
84HP AM840KXVGGH1EU
3
1
2
86HP AM860KXVGGH1EU
3
1
2
88HP AM880KXVGGH1EU
3
1
2
90HP AM900KXVGGH1EU
3
3
NOTE
•
Make sure to use an indoor unit that is compatible with DVM S.
•
Indoor units can be connected within the range indicated in following table.
•
If the total capacity of the connected indoor units exceeds the indicated maximum capacity, cooling and heating
capacity of the indoor unit may decrease.
•
Total capacity of the connected indoor units can be allowed from 50% to 130% of the total outdoor unit capacity.
0.5 ×Σ (Outdoor unit capacity) ≤ Total capacity of the connected indoor units ≤ 1.3 × Σ (Outdoor unit capacity)
❇
❇
You can connect maximum 64 indoor units to the outdoor unit. Maximum quantity of connectable indoor unit is
set to 64 since outdoor unit only support up to 64 communication address. Indoor unit address can be assigned
from 0~63. If the indoor unit address was assigned from 64~79, E201 error will occur.
❇
❇
Maximum 32 Wall-mount type indoor units with EEV (AM***FNQDEH***, AM***JNVDKH*) can be connected.
•
In case of combining modules more than 90 HP, please consult the manufacturer when connecting the indoor unit
and deciding on piping length in accordance with design of the building.