Installing the unit

IMPORTANT:  When installing the unit, always remember to connect first the refrigerant tubes, then the electrical lines.  

Always disassemble the electric lines before the refrigerant tubes.

f

Upon receipt, inspect the product to verify that it has not been damaged during transport. If the product appears damaged, DO NOT 
INSTALL it and immediately report the damage to the carrier or retailer (if the installer or the authorized technician has collected the 
material from the retailer.)

f

After completing the installation, always carry out a functional test and provide the instructions on how to operate the air conditioner 
to the user.

f

Do not use the air conditioner in environments with hazardous substances or close to equipment that release free flames to avoid the 
occurrence of fires, explosions or injuries.

f

Our units should be installed in compliance with the spaces shown in the installation manual, to ensure accessibility from both sides 
and allow repairs or maintenance operations to be carried out. The unit’s components should be accessible and easy to disassemble 
without endangering people and objects.
For this reason, when provisions of the installation manual are not complied with, the cost required to access and repair the 
units (in SAFETY CONDITIONS, as set out in prevailing regulations) with harnesses, ladders, scaffolding or any other elevation 
system will NOT be considered part of the warranty and will be charged to the end customer.

Power supply line, fuse or circuit breaker

f

Always make sure that the power supply is compliant with current safety standards. Always install the air conditioner in compliance 
with current local safety standards.

f

Always verify that a suitable grounding connection is available.

f

Verify that the voltage and frequency of the power supply comply with the specifications and that the installed power is sufficient to 
ensure the operation of any other domestic appliance connected to the same electric lines.

f

Always verify that the cut-off and protection switches are suitably dimensioned.

f

Verify that the air conditioner is connected to the power supply in accordance with the instructions provided in the wiring diagram 
included in the manual.

f

Always verify that electric connections (cable entry, section of leads, protections…) are compliant with the electric specifications and 
with the instructions provided in the wiring scheme. Always verify that all connections comply with the standards applicable to the 
installation of air conditioners.

f

Devices disconnected from the power supply should be completely disconnected in the condition of overvoltage category.

t

Make sure that you earth the cables.

 

- Do not connect the earth wire to the gas pipe, water pipe, lighting rod or telephone wire. If earthing is not complete, 

electric shock or fire may occur.

t

Install the circuit breaker.

 

- If the circuit breaker is not installed, electric shock or fire may occur.

t

Make sure that the condensed water dripping from the drain hose runs out properly and safely.

t

Install the power cable and communication cable of the indoor and outdoor unit at least 1m away from the electric 
appliance.

t

Install the indoor unit away from lighting apparatus using the ballast.

 

- If you use the wireless remote controller, reception error may occur due to the ballast of the lighting apparatus.

t

Do not install the air conditioner in following places.

 

- Place where there is mineral oil or arsenic acid. Resin parts flame and the accessories may drop or water may leak. 

The capacity of the heat exchanger may reduce or the air conditioner may be out of order.

 

- The place where corrosive gas such as sulfurous acid gas generates from the vent pipe or air outlet.

t

The copper pipe or connection pipe may corrode and refrigerant may leak.

 

- The place where there is a machine that generates electromagnetic waves. The air conditioner may not operate 

normally due to control system.

 

- The place where there is a danger of existing combustible gas, carbon fiber or flammable dust.

t

The place where thinner or gasoline is handled. Gas may leak and it may cause fire.

CAUTION

Summary of Contents for AM036JNCDCH

Page 1: ......

Page 2: ...alidatethewarranty f Theairconditionershouldbeusedonlyfortheapplicationsforwhichithasbeendesigned theindoorunitisnotsuitabletobe installedinareasusedforlaundry f Donotusetheunitsifdamaged Ifproblemsoccur switchtheunitoffanddisconnectitfromthepowersupply f Inordertopreventelectricshocks firesorinjuries alwaysstoptheunit disabletheprotectionswitchandcontactSAMSUNG stechnical supportiftheunitproduces...

Page 3: ...therdomesticapplianceconnectedtothesameelectriclines f Alwaysverifythatthecut offandprotectionswitchesaresuitablydimensioned f Verifythattheairconditionerisconnectedtothepowersupplyinaccordancewiththeinstructionsprovidedinthewiringdiagram includedinthemanual f Alwaysverifythatelectricconnections cableentry sectionofleads protections arecompliantwiththeelectricspecificationsand withtheinstructionsp...

Page 4: ...hortroutingoftherefrigeranttubingandwiringtotheoutdoorunit f Thereshouldbenoflammablegas alkaline substancespresentintheair f Avoidlocationwhereobstaclespreventinggoodaircirculationarepresent f Noisepreventionshouldbeconsideredindeterminingtheunit slocation f Thestructure wheretheunitistobeinstalledshouldbestrongenoughtosupporttheweightoftheunit f Rigidwallwithoutvibration f Whereitisnotexposedtod...

Page 5: ...8 3 Drainpipeconnection ODø25 0 98 IDø020 0 79 A B 03 94 100 9 25 235 4 33 110 4 92 125 1 10 24 260 2 60 66 5 29 134 3 3 54 90 6 14 156 26 57 675 3 01 10 28 01 65 42 2 Dimensionoftheindoorunit Model Dimension A B AM036JNCDCH 53 15 1350 51 10 1298 AM048JNCDCH 64 96 1650 62 91 1598 Unit Inch mm ...

Page 6: ...rangethedrainhoseso thatitisleveledlowerthanthedrainhoseconnectingportofthe indoorunit Forproperdrainageofcondensate givea2 Thegapbetween thelowerendoftheindoorunitandtheceilingshouldbe 0 91inch 23mm ormore slanttothesideoftheunitwhichwillbe connectedwiththedrainhoseasshowninthefigure NOTE t Ensurethattheceilingisstrongenoughtosupporttheweightof theindoorunit t Beforehangingtheunit testthestrength...

Page 7: ...epinchpipeonthepipesandconnecttheassemblypipes toeachpipe tighteningthenuts firstmanuallyandthenwithatorque wrench aspannerapplyingthefollowingtorque OuterDiameter D Torque mm inch tN MCGtGU ø6 35 1 4 18 13 3 ø9 52 3 8 42 31 0 ø12 7 1 2 55 40 6 ø15 88 5 8 65 47 9 ø19 05 3 4 100 73 8 Mustapplyrefrigerantoilontheflaringareatopreventaleak NOTE 3 Besurethattheremustbenocrackorkinkonthebendedarea Ifnec...

Page 8: ...2 0 09 Pipe Flare 5 Checkthattheflaringiscorrect referringtotheillustrationsbelowforexamplesofincorrectflaring Uneven Thickness Cracked DamagedSurface Inclined Correct 6 Alignthepipesandtightentheflarenutsfirstmanuallyandthenwithatorquewrench applyingthefollowingtorque Valve Flarenut Valvecap Pressureportcap Valveneedle Pressureport Wrench mm tN Wrench mm tN Wrench mm tN Wrench mm tN Wrench mm tN ...

Page 9: ...havecheckedthattherearenoleaksinthesystem you caninsulatethepipingandhose 1 Toavoidcondensationproblems placeAcrylonitrileButadienRubber separatelyaroundeachrefrigerantpipe 2 Windinsulatingtapearoundthepipesanddrainhoseavoidingto compresstheinsulationtoomuch 3 Finishwrappinginsulatingtapearoundtherestofthepipesleadingto theoutdoorunit 4 Thepipesandelectricalcablesconnectingtheindoorunitwiththe out...

Page 10: ... 05 3 4 19 3 4 25 1 f Wheninstallinginsulationinplacesandconditionsbelow usethesameinsulationthatisusedforhighhumidity conditions Geologicalcondition Highhumidityplacessuchasshoreline hotspring nearlakeorriver andridge whenthepartofthebuildingis coveredbyearthandsand Operationpurposecondition Restaurantceiling sauna swimmingpooletc Buildingconstructioncondition Theceilingfrequentlyexposedtomoistur...

Page 11: ...f Insertthedrainhosetobottomoftheoutfallofwaterbasin f Lockflexiblehoseclampofthedrainhoseaccordingtothefigure f Windandwrapflexiblehoseclampanddrainhosefullywiththermalinsulationsponge fixbothendsofexternallayer withribbonforthermalinsulation f Afterbeinginstalled drainhosemustbeinsulatedfullybyheatinsulatingmaterial Tobeprovidedatsite Flexiblehoseclamp ofdrainhose Jointofdrainhose Drainhose Drai...

Page 12: ...Unit Wired Remote Controller EEV kit K Ceiling wall mounted indoor unit K ELCB Essential Installation WARNING Power off before connecting any wires Indoor PBA will be damaged while V1 V2 F3 F4 short each other Norminal dimensions for cable inch2 Norminal dimensions for screw inch B D d1 E F L d2 t Standard dimension inch Allowance inch Standard dimension inch Allowance inch Standard dimension inch...

Page 13: ...um length within 10 power drop among indoor units 7 coef 1 55 7 Lk Distance among each indoor unit m ft Ak Power cable specification mm2 inch2 ik Running current of each unit A Coef 35 6 Lk ik 10 of input voltage V 1000 Ak n k 1 Example of Installation Total power cable length L 328ft 100m Running current of each units 1 A Total 10 indoor units were installed X Apply following equation Coef 35 6 L...

Page 14: ...he indoorandoutdoorunitsintheironpipe t Connectthepowercabletotheauxiliarycircuitbreaker Anallpoledisconnectionfromthepowersupplymustbeincorporatedinthefixedwiring 1 8 3mm t Youmustkeepthecableinaprotectiontube t Keepdistancesof2 50mm ormorebetweenpowercableandcommunicationcable t Maximumlengthofpowercablesaredecidedwithin10 ofpowerdrop Ifitexceeds youmustconsideranotherpower supplying method t Th...

Page 15: ...xintheindoorunit Seethe picture 2 AttachtheInterfacemodulePCBtothecaseinthecontrolboxoftheindoorunit then connectthepowerandthecommunicationcablebetweentheInterfacemoduleand theindoorunit 3 IfyouinstallaInterfacemoduletoanindoorunit everyoutdoorunitwhichisconnected toanindoorunitcanbecontrolledsimultaneously 4 EachindoorunitconnectedtothesamecentralizedcontrollerhasitsownInterface module ...

Page 16: ...7 SEG8 SEG9 SEG10 SEG11 SEG12 0 X X X X X 1 X X X X X SEG13 SEG14 SEG15 SEG16 SEG17 SEG18 SEG19 SEG20 SEG21 SEG22 SEG23 SEG24 2 X X X X X 3 X X X X X On SEG1 12 Off SEG13 24 On Auto Auto Off Theprocedureofoptionsetting t Option setting is available from SEG1 to SEG 24 t SEG1 SEG7 SEG13 SEG19 are not set as page option t Set the SEG2 SEG6 SEG8 SEG12 as ON status and SEG14 18 SEG20 24 as OFF status ...

Page 17: ...ected in rotation On Dry On Dry 6 Setting Fan mode Press Mode button to be changed to FAN mode in the ON status On Fan 7 Setting SEG9 SEG10 option Press Low Fan button to enter SEG9 value Press High Fan button to enter SEG10 value Each time you press the button will be selected in rotation On Fan On Fan 8 Setting Heat mode Press Mode button to be changed to HEAT mode in the ON status On Heat 9 Set...

Page 18: ... button to enter SEG22 value Each time you press the button will be selected in rotation Off Fan Off Fan 18 Setting Heat mode Press Mode button to be change to HEAT mode in the OFF status Off Heat 19 Setting SEG23 SEG24 mode Press Low Fan button to enter SEG23 value Press High Fan button to enter SEG24 value Each time you press the button will be selected in rotation Off Heat Off Heat SEG16 SEG18 ...

Page 19: ...ication Details Indication Details Indication Details Indication Details 0 A 0 No Main address 0 9 100 digit 0 9 10 digit 0 9 Aunit digit 1 Main address setting mode Option SEG7 SEG8 SEG9 SEG10 SEG11 SEG12 Explanation PAGE __ SettingRMCaddress __ Groupchannel 16 Groupaddress Remote Controller Display On Fan On Heat On Heat Indication andDetails Indication Details Indication Details Indication Deta...

Page 20: ...l control External control output External heater On or Off signal S Plasma ion Buzzer Number of hours using filter SEG19 SEG20 SEG21 SEG22 SEG23 SEG24 3 Individual control of a remote controller Heating setting compensation Removing condensated water in heating mode EEV Step of stopped unit during oil return defrost mode Motion detect sensor X 1WAY 2WAY 4WAY MODEL Drain pump SEG8 will be set to U...

Page 21: ...etails Indication Details Indication Details Useof External room temperature sensor Minimizingfan operationwhen thermostatisoff 0 2 0 Disuse 0 Disuse Disuse 0 Disuse 0 Disuse 1 Use Disuse 1 RPM compensation 1 Use 2 Disuse Use 1 1 Use 2 Highceiling KIT 3 Use Use 1 Option SEG7 SEG8 SEG9 SEG10 SEG11 SEG12 Explanation PAGE Useofdrainpump Useofhotwater heater EEVStepwhenheating stops Remote Controller ...

Page 22: ...on Removing condensatedwaterinheatingmode EEVStepofstopped unitduringoilreturn defrostmode Motiondetectsensor Remote Controller Display Off Dry Off Fan Off Fan Off Heat Indication andDetails Indication Details Indication Details Indication Details Indication Details Indication Details HeatingSetting Compensation Removing Condensated Waterin Heating Mode 3 0or1 channel1 0 Default 4 Disuse 0 Default...

Page 23: ...or3isusedasexternalheaterOn Offsignal thesignalformonitoringexternalcontactcontrolwillnotbeoutput 2 Fanisturnedoncontinuallywhentheexternalheateristurnedon 3 Fanisturnedoffwhentheexternalheateristurnedonwithcoolingonlyindoorunit Coolingonlyindoorunit Tousethisoption installtheModeSelectswitch MCM C200 ontheoutdoorunitandfixitascoolmode g IfFanissettooffforcoolingonlyindoorunitbysettingtheSEG9 3orS...

Page 24: ...F 2 5 C 5 6 3 F 3 5 C 6 5 4 F 3 C 6 5 4 F 3 C 6 7 2 F 4 C 7 6 3 F 3 5 C 7 6 3 F 3 5 C 7 8 1 F 4 5 C Option SEG7 SEG8 SEG9 SEG10 SEG11 SEG12 Explanation PAGE WhensettingSEG3 Standardformode changingCooling Heatingmode WhensettingSEG3 Timerequiredfor modechange Compensationoption forLongpipeorheight diffferencebetween indoorunits Remote Controller Display On Dry On Fan On Fan Indication andDetails I...

Page 25: ...at ison andturnedoffwhentheheatingthermostatisoff e g 2 Setting02seriesSEG15 2 Setting05seriesSEG18 A Roomtemp settemp f heatingcompensationtemp Externalheateristurnedonwhenthetemperatureismaintainedas8 1 F 4 5 C for10minutes Roomtemp settemp f heatingcompensationtemp Externalheateristurnedoffwhenthetemperatureismaintainedas8 1 F 4 5 C 1 8 F 1 C 1 CistheHysteresisforOn Off selection Option SEG13 S...

Page 26: ...statusismaintainedduringthetimewithSEG9 A SetwithSEG4 B SetwithSEG5 C SetwithSEG6 D SetwithSEG8 Cooling Thermo Off Heating Thermo Off Cooling Thermo On Heating Thermo On B C D Ts A c a Temp d b Standardtemp forHeating Standardtemp forCooling Standardtemp for Heating Cooling Standardtemp forCooling Heating Settemp forAutomode Settinganindoorunitaddressandinstallationoption ...

Page 27: ...Explanation PAGE MODE Theoptionmodeyou wanttochange Thetens digitofan optionSEGyouwill change Theunitdigitofan optionSEGyouwill change Changedvalue Indication 0 D 2 1 7 1 t When changing a digit of an indoor unit address setting option set the SEG3 as A t When changing a digit of indoor unit installation option set the SEG3 as 2 Ex When setting the buzzer control into disuse status t If you are us...

Page 28: ...llError Communicationerrorbetweenindoorunits EEPROMerror EEPROMoptionerror Erroroftemperaturesensorinindoorunit open short ErrorofoutdoorUnit Self Diagnosis Erroroftheindoorunitpipesensor Highpressureblockageerror Indoorfanerror Thermalfuseopenerror IndoorunitfloatS W2nddetection On Flickering XOff f If you turn off the air conditioner when the LED is flickering the LED is also turned off f Ifyour...

Page 29: ...tweenoutdoorunitinv mainmicom ForPF 4 6controller errorwillbe determinedfromthetimewhencompressoristurnedon E221 Erroronoutdoortemperaturesensor ShortorOpen E231 ErroronoutdoorCONDOUTsensor ShortorOpen E251 Errorondischargetemperaturesensorofcompressor1 ShortorOpen E320 ErroronOLPsensor ShortorOpen E403 Compressordownduetofreezeprotectioncontrol E404 Systemstopduetooverloadprotectioncontrol E416 S...

Page 30: ...oronIPMHeatSinksensorofinverter1 ShortorOpen E475 Erroroninverterfan2 E484 PFCOverload Overcurrent Error E485 Erroroninputcurrentsensorofinverter1 ShortorOpen E500 IPMoverheaterroroninverter1 E508 Smartinstallisnotinstalled E554 Gasleakdetected E556 Errorduetomismatchingcapacityofindoorandoutdoorunit E557 DPMremotecontrolleroptionerror E590 InverterEEPROMCheckSumerror E660 InverterBootCodeerror Tr...

Page 31: ...31 ENGLISH ...

Page 32: ...This product is RoHS compliant DB68 05464A 00 EN ES FR PT ...

Page 33: ...imagine the possibilities ThankyouforpurchasingthisSamsungproduct This manual is made with 100 recycled paper Ceiling Type Series AM777JNCDCH777 Air Conditioner installation manual ...

Reviews: