Product Specifications
Samsung Electronics
35
Model
AM128FNMDEH
*
AM140FNMDEH
*
AM160KNMDEH
*
Power Supply
ø/V/Hz
1/220~240/50
1/220~240/50
1/220~240/50
Mode*1)
HP / HR
HP / HR
HP / HR
Performance
Capacity
Cooling*2)
kW
12.8
14
16.0
Btu/h
43,600
47,700
54,000
Heating*3)
kW
13.8
16.0
18.0
Btu/h
47,000
54,500
60,000
Condensate (with High fan speed)
Liters/h
4.95
5.1
-
Power
Input
W
370
410
485
Running Current
A
1.67
1.86
2.24
Sound Level
Sound Pressure *4)
dB(A)
50
50
53
Fan
Type
-
Sirocco Fan
Sirocco Fan
Sirocco Fan
Motor
Model
-
Y7S423C015
Y7S423C015
Y7S423C015
Type
-
Non Feedback SSR
Non Feedback SSR
Non Feedback SSR
Output
W
-
-
-
Airflow Rate
Cooling (High)
m3/min
32.0
37.0
39.5
Heating (High)
m3/min
31.0
36.0
42.0
External Static
Pressure
Standard
(Min.~Max)
mmH2O
8(4~12)
8(4~12)
8(4~14)
Refrigerant
Type
-
R410A
R410A
R410A
Control Method
-
EEV
EEV
EEV
Temperature Control
-
Micom&Thermistors
Micom&Thermistors
Micom&Thermistors
Safety Devices
-
Fuse
Fuse
Fuse
Piping
Connections
Liquid (Flare)
ø, mm
9.52
9.52
9.52
Gas (Flare)
ø, mm
15.88
15.88
15.88
Drain
ø, mm
VP25 (OD 32,ID 25)
VP25 (OD 32,ID 25)
VP20 (OD 25, ID 20)
Weight
Net Weight
kg
52.0
52.0
50
Shipping Weight
kg
59.0
59.0
57
Dimensions
Net Dimensions (W x H x D)
mm
1,200x360x650
1,200x360x650
1,200x360x650
Shipping Dimensions (W x H x D)
mm
1480×790×420
1480×790×420
1480×790×420
Functions
Auto Restart
-
O
O
O
Auto Swing
-
X
X
X
Group/Individual Control
-
O
O
O
External Contact Control
-
O
O
O
Trouble Shooting by LED
-
X
X
X
Standard
Accessories
Installation Manual
-
O
O
O
Operation Manual
-
O
O
O
Pattern Sheet for Installation
-
X
X
X
Flexible Drain Hose
-
O
O
O
Filter / Safety Grille
-
Filter (Washable)
Filter (Washable)
Filter (Washable)
Optional
Accessories
Wireless Remote Controller
-
MR-DH00
MR-DH00
MR-DH00
Duct Receiver
Kits
Receiver
-
MRK-A10
MRK-A10
MRK-A10
Receiver Wire
-
MRW-10A
MRW-10A
MRW-10A
Wired Remote
Controller
Simplified
-
MWR-WE10N
MWR-WE10N
MWR-WE10N
External Contact Interface Module
-
MIM-B14
MIM-B14
MIM-B14
Drain Pump
MDP-M075SGU2D
MDP-M075SGU2D
MDP-M075SGU2D
*1) Mode
- HP : Heat Pump, HR : Heat Recovery
*2) Nominal cooling capacities are based on;
- Indoor temperature : 27˚C DB, 19˚C WB
- Outdoor temperature : 35˚C DB, 24˚C WB, Equivalent refrigerant piping : 7.5m, Level differences : 0m
*3) Nominal heating capacities are based on;
- Indoor temperature : 20˚C DB, 15˚C WB
- Outdoor temperature : 7˚C DB, 6˚C WB, Equivalent refrigerant piping : 7.5m, Level differences : 0m
*4) Sound pressure was acquired in a dead room. Thus actual noise level may be different depending on the installation conditions.
*5) Specifications may be subject to change without prior notice for product improvement.