Setting outdoor unit option switch and key function
Setting outdoor unit option switches : A TYPE
Terminal blocks (R1, R2) for connection with the Upper Controller
(DMS, Touch, On/Off Controller, etc.)
Do not connect the power and communication wires to these terminal blocks
f
Setting outdoor install option
Step
Button
Display
Description
Note
Quantity of indoor units
Setting required
Step1
Press (K1+K2)
for 2 seconds
Ready to set
-
Step2
K2 x n times
X
Tens digit (0 ~ 6) Ex) 03 : 3 units
10 : 10 units
K4 x n times
X
Ones digit (0 ~ 9)
* K4 : Press for 2 seconds - automatic detection of indoor units' quantity
Step3
If it is heat recovery model, go to step 4.
Otherwise, press K2 button for 2 seconds to save & exit.
(system will be reset)
No
Yes
Save (Step 8)
Heat Recovery?
Quantity of HR Changer/
MCUs
(Step 4 ~ 5)
The setting of heat
recovery system
(Step 6 ~7)
Quantity of indoor units
(Step 2 ~ 3)
Start (Step 1)