25
English
Installation Pr
oc
edur
e
Please refer to the EEV step table below for the system (for heating) at stop.
Indication
0
2
3
4
5
6
7
8
9
A
B
Stopped
Unit's
EEV step
Wall
MountedWith EEV
A Step
100
90
100
110
120
130
160
200
250
300
400
B Step
125
160
160
160
160
160
160
200
250
300
400
Other Indoor Units except for
wall mounted with EEV
Default
No Function
(*4)
When the following 2 or 3 is used as external heater On/Off signal, the signal for monitoring external contact control will not
be output.
2: Fan is turned on continually when the external heater is turned on.
3: Fan is turned off when the external heater is turned on with cooling only indoor unit
Cooling only indoor unit: To use this option, install the Mode Select switch(MCM-C200) on the outdoor unit and fix it as
cool mode.
‐
If Fan is set to off for cooling only indoor unit by setting the SEG15=3, you need to use an external sensor or wired
remote controller sensor to detect indoor temperature exactly.
(*5)
When indoor unit is in cooling or Dry mode, The output signal is “ON”
(*6)
For free cooling control, Economizer controller is required.
(*7)
Default setting value
‐
4Way Cassette, Mini 4Way Cassette: 5 °C
‐
Other indoor units: 2 °C
(*8)
This function can be applied to 4 Way Cassette and Mini 4 Way Cassette only. If the air conditioner operates the heating
mode immediately after finishing the cooling mode, the condensated water in the drain pan becomes water vapor by the
heat of the indoor unit heat exchanger. Since the water vapor might be condensed on the indoor unit, which may fall into
a living space, use this function to get rid of the water vapor out of the indoor unit by operating the fan (for maximum 20
minutes) even when the indoor unit is turned off after cooling mode is turned to heating mode.
DB68-08953A-00_IM_DVM QMD_EU_EN_.indd 25
2020-02-10 오후 4:23:11