background image

25

English

Installation Pr

oc

edur

e

Please refer to the EEV step table below for the system (for heating) at stop.

Indication

0

2

3

4

5

6

7

8

9

A

B

Stopped 

Unit's 

EEV step

Wall 

MountedWith EEV 

A Step

100

90

100

110

120

130

160

200

250

300

400

B Step

125

160

160

160

160

160

160

200

250

300

400

Other Indoor Units except for 

wall mounted with EEV

Default

No Function

(*4)

   When the following 2 or 3 is used as external heater On/Off signal, the signal for monitoring external contact control will not 

be output. 

2: Fan is turned on continually when the external heater is turned on. 

3:  Fan is turned off when the external heater is turned on with cooling only indoor unit 

Cooling only indoor unit: To use this option, install the Mode Select switch(MCM-C200) on the outdoor unit and fix it as 

cool mode.

 

If Fan is set to off for cooling only indoor unit by setting the SEG15=3, you need to use an external sensor or wired 

remote controller sensor to detect indoor temperature exactly.

(*5)

  When indoor unit is in cooling or Dry mode, The output signal is “ON”

(*6)

  For free cooling control, Economizer controller is required.

(*7)

  Default setting value

 

4Way Cassette, Mini 4Way Cassette: 5 °C

 

Other indoor units: 2 °C

(*8)

   This function can be applied to 4 Way Cassette and Mini 4 Way Cassette only. If the air conditioner operates the heating 

mode immediately after finishing the cooling mode, the condensated water in the drain pan becomes water vapor by the 

heat of the indoor unit heat exchanger. Since the water vapor might be condensed on the indoor unit, which may fall into 

a living space, use this function to get rid of the water vapor out of the indoor unit by operating the fan (for maximum 20 

minutes) even when the indoor unit is turned off after cooling mode is turned to heating mode.

DB68-08953A-00_IM_DVM QMD_EU_EN_.indd   25

2020-02-10   오후 4:23:11

Summary of Contents for AM TNVD Series

Page 1: ...anual AM TNVD AM TNAD Thank you for purchasing this Samsung air conditioner Beforeoperatingthisunit pleasereadthisinstallationmanualcarefullyandretainitforfuturereference DB68 08953A 00_IM_DVM QMD_EU_...

Page 2: ...aring the pipes 8 Step 7 Performing leak test 9 Step 8 Wrapping the pipes with the insulation 9 Step 9 Installing the drain hose 10 Step10 Optional Changing direction of the drain hose 10 Step11 Conne...

Page 3: ...if the unit produces smoke if the power cable is hot or damaged or if the unit is very noisy Always remember to inspect the unit electric connections refrigerant tubes and protections regularly These...

Page 4: ...power cable modification extension wiring and multiple wire connection It may cause electric shock or fire due to poor connection poor insulation or current limit override When extension wiring is re...

Page 5: ...the remote control can be operated well A place where the air filter can be replaced easily CAUTION Do not install the product with EEV commercial model in a quiet place such as bedroom hotel and hosp...

Page 6: ...plate to the wall giving attention to the weight of the indoor unit Level Screw Location x 4ea NOTE If you mount the plate to a concrete wall by using plastic anchors make sure that gaps between the w...

Page 7: ...h the cut edges 3 Remove the protection caps of the pipes and connect the assembly pipe to each pipe Tighten the nuts first with yourhands and then with a torque wrench applying the following torque R...

Page 8: ...ring tool Unit mm Outer diameter A Flare tool for R410Aclutch type Conventional flare tool Clutch type Wing nut type 6 35 0 0 5 1 0 1 5 1 5 2 0 9 52 0 0 5 1 0 1 5 1 5 2 0 12 7 0 0 5 1 0 1 5 1 5 2 0 15...

Page 9: ...the pipe hose and cables Then place the indoorunit on the installation plate 1 To avoid condensation problems place heat resistant poly ethylene foam separately around each refrigerant pipe in the lo...

Page 10: ...e NOTE If you don t use the other drain hose hole block it with a rubber stopper 4 Pass the drain hose underthe refrigerant pipe keeping the drain hose tight 5 Pass the drain hose through the hole in...

Page 11: ...es at the back side of the indoor unit when installing the wired remote control V1 F1 1 L 2 N F2 F1 1 L 2 N 1 L 2 N F2 F1 F2 F1 F2 F1 F2 F1 F2 N L N L N L N L F1 F2 1 L 2 N F1 F2 F1 1 L 2 N F2 F1 1 L...

Page 12: ...0 1 s 2 5 mm 2 5 mm 0 75 1 5 mm Refer to the unit nameplate for rating current Decide the capacity of ELCB or MCCB ELB by below formula Power supply cords of parts of appliances for outdoor use shall...

Page 13: ...t local and national regulations Wire size must comply with local and national code For the power cable use the grade of H07RN F or H05RN F materials You should connect the power cable into the power...

Page 14: ...terminal screws Tightening torque N m kgf cm M 3 5 0 8 1 2 8 0 12 0 M 4 1 2 1 8 12 0 18 0 Step12 Optional Extending the power cable 1 Prepare the following tools Tools Spec Shape Crimping pliers MH 1...

Page 15: ...tube in the middle of the insulation tape 40 mm Insulation tape Method1 35 mm Insulation tape Method 2 6 Apply heat to the contraction tube to contract it Contraction tube Method1 Contraction tube Me...

Page 16: ...imer Wind Free Direction 1 Remove batteries from the remote control 2 Insert batteries and enterthe option setting mode while pressing High Temp button and Low Temp button 3 Check if you have entered...

Page 17: ...us 5 Setting SEG6 SEG8 option a Press Low Fan button to enterSEG6 value b Press High Fan button to enterSEG8 value Each time you press the button will be selected in rotation SEG6 SEG8 6 Setting Fan m...

Page 18: ...ch time you press the button will be selected in rotation SEG16 SEG17 14 Setting Dry mode Press Mode button to be changed to Dry mode in the OFF status 15 Setting SEG18 SEG20 option a Press Low Fan bu...

Page 19: ...t is correct ornot SEG2 SEG3 SEG21 SEG22 SEG23 SEG24 SEG4 SEG5 SEG6 SEG8 SEG9 SEG10 SEG11 SEG12 SEG14 SEG15 SEG16 SEG17 SEG18 SEG20 6 Press the button with the direction of remote control forset Forth...

Page 20: ...Indication and Details Indication Details Indication Details Indication Details Indication Details 1 0 No RMC address RMC1 0 F RMC2 0 F 1 RMC address setting mode CAUTION When A F is entered to SEG5...

Page 21: ...will be set as 0 SEG5 central control option is basically set as 1 Use so you don t need to set the central control option additionally However if the central control is not connected but it doesn t i...

Page 22: ...atisoff 0 2 0 Default Default 1 Use Disuse 2 Disuse Use Heating 1 3 Use Use Heating 1 4 Disuse Use Cooling 1 5 Use Use Cooling 1 6 Disuse Use Heating Cooling 1 7 Use Use Heating Cooling 1 8 Disuse Use...

Page 23: ...e Use 4 MaintainbladestatusinWind Freemode Useeveryfanmode Disuse 5 Coolingoperationbyopening theblade Useeveryfanmode Disuse 6 MaintainbladestatusinWind Freemode UseonlyWind Free mode Disuse 7 Coolin...

Page 24: ...turnorNoise decreasingindefrost mode 5 5 C Use 8 1 Minimizing fan operation when thermostat is off Fan operates for 20 seconds at an interval of 5 minutes in heat mode Fan stops or operates Ultra low...

Page 25: ...to off for cooling only indoor unit by setting the SEG15 3 you need to use an external sensor orwired remote controller sensor to detect indoor temperature exactly 5 When indoorunit is in cooling orD...

Page 26: ...G20 SEG21 SEG22 SEG23 SEG24 3 Forced FAN Operation for Heating and Cooling 05 series installation option Detailed Option No 02XXXX 1XXXXX 2XXXXX 3XXXXX Option SEG1 SEG2 SEG3 SEG4 SEG5 SEG6 Explanation...

Page 27: ...C 3 11min 4 3 C 4 13min 2 1 Heightdifference is15 30mor 2 Distanceis50 110m 2 Use 5 3 5 C 5 15min 6 4 C 6 20min 7 4 5 C 7 30min Option SEG13 SEG14 SEG15 SEG16 SEG17 SEG18 Explanation Controlvariablesw...

Page 28: ...tion 1 2 Distance The difference between the pipe length of the indoorunit installed at farthest place from an outdoorunit and the pipe length of the corresponding indoorunit from an outdoorunit Forex...

Page 29: ...forCooling A Set with SEG4 C B Set with SEG5 C C Set with SEG6 C D Set with SEG8 C Standard temp for Cooling Heating Cooling thermo off Cooling thermo on Heating thermo off Heating thermo on Standard...

Page 30: ...ress setting option set the SEG3 as A When changing a digit of indoor unit installation option set the SEG3 as 2 Ex When setting the buzzercontrol into disuse status Option SEG1 SEG2 SEG3 SEG4 SEG5 SE...

Page 31: ...ditioner operates according to the selected mode or function 4 Press the button and check the following The airflow blades work properly 5 Press the button and check the following The airflow blades w...

Page 32: ...ensor E221 2 Erroron cond sensor E237 3 Erroron discharge sensor E251 Otheroutdoorunit sensorerrors that are not on the above list 1 When there is no communication between the indoorand outdoorunits f...

Page 33: ...ve 1st detection E180 15 Simultaneous opening of cooling heating MCU SOLvalve 2nd detection E181 Otheroutdoorunit self diagnosis errors that are not on the above list External contact input error E665...

Page 34: ...DB68 08953A 00_IM_DVM QMD_EU_EN_ indd 34 2020 02 10 4 23 12...

Reviews: