19
English
Installation Pr
oc
edur
e
3
Insert both sides of core wire of the power cable into
the connection sleeve.
•
Method 1
: Push the core wire into the sleeve from
both sides.
•
Method 2
: Twist the wire cores together and push it
into the sleeve.
Connection sleeve
Method 1
Connection sleeve
Method 2
CAUTION
• If cable wires are connected without using connecting
sleeves, their contact area becomes reduced, or
corrosion develops on the outer surfaces of the wires
(copper wires) over a long time. This may cause an
increase of resistance (reduction of passing current)
and consequently may result in a fire.
4
Using a crimping tool, compress the two points and
flip it over and compress another two points in the
same location.
• The compression dimension should be 8.0.
Compression
dimension
• After compressing it, pull both sides of the wire to
make sure it is firmly pressed.
Compress it 4 times.
5 mm
Method 1
Compress it 4 times.
5 mm
Method 2
5
Wrap it with the insulation tape twice or more and
position your contraction tube in the middle of the
insulation tape.
Method 2
Method 1
Insulation tape
40 mm
Insulation tape
35 mm
6
Apply heat to the contraction tube to contract it.
Method 2
Method 1
Contraction tube
Contraction tube
7
After tube contraction work is completed, wrap it with
the insulation tape to finish.
Three or more layers of insulation are required.
Method 2
Method 1
Insulation tape
Insulation tape
CAUTION
• Make sure that the connection parts are not exposed
to outside.
• Be sure to use insulation tape and a contraction tube
made of approved reinforced insulating materials
that have the same level of withstand voltage with
the power cable. (Comply with the local regulations on
extensions.)