32
Installation Procedure
Instal
lation Pr
oc
edur
e
English
05 series installation option (Detailed)
Option No. : 05XXXX-1XXXXX-2XXXXX-3XXXXX
Option
SEG1
SEG2
SEG3
SEG4
SEG5
SEG6
Explanation
PAGE
MODE
Use of Auto Change Over
for HR only in Auto mode /
Use of Cooling only indoor
unit of HR
(When setting SEG3)
Standard heating temp
Offset
(When setting SEG3)
Standard cooling temp
Offset
(When setting SEG3)
Standard for mode change
Heating → Cooling
Indication
and Details
Indication Details Indication
Details
Indication
Details
Indication
Details
Indication
Details
Indication
Details
0
5
0
Follow
product
option
0
32 °F (0°C)
0
32 °F (0°C)
0
33.8 °F (1°C)
1
32.9 °F (0.5 °C)
1
32.9 °F (0.5 °C)
1
34.7 °F (1.5°C)
1
Use Auto
Change Over
for HR only
2
33.8 °F (1°C)
2
33.8 °F (1°C)
2
35.6 °F (2°C)
3
34.7 °F (1.5°C)
3
34.7 °F (1.5°C)
3
36.5 °F
(2.5°C)
4
35.6 °F (2°C)
4
35.6 °F (2°C)
4
37.4 °F (3°C)
2
Use Cooling
only indoor
unit for HR
5
36.5 °F (2.5°C)
5
36.5 °F (2.5°C)
5
38.3 °F
(3.5°C)
6
37.4 °F (3°C)
6
37.4 °F (3°C)
6
39.2 °F (4°C)
7
38.3 °F (3.5°C)
7
38.3 °F (3.5°C)
7
40.1 °F
(4.5°C)
Option
SEG7
SEG8
SEG9
SEG10
SEG11
SEG12
Explanation
PAGE
(When setting SEG3)
Standard for mode
change Cooling →
Heating
(When setting SEG3)
Time required for mode
change
Compensation option
for Long pipe or height
difference between indoor
units
MTFC (*3)
-
Indication
and Details
Indication Details Indication
Details
Indication
Details
Indication
Details
Indication
Details
-
1
0
33.8 °F
(1°C)
0
5min
0
Default
0
Default
-
1
34.7 °F
(1.5°C)
1
7min
1
(*1) Height
difference is
more than
30m or (*2)
Distance is
longer than
110m
2
35.6 °F
(2°C)
2
9min
3
36.5 °F
(2.5°C)
3
11min
4
37.4 °F
(3°C)
4
13min
2
(*1) Height
difference is
15~30m or
(*2) Distance
is 50~110m
2
Use
-
5
38.3 °F
(3.5°C)
5
15min
6
39.2 °F
(4°C)
6
20min
7
40.1 °F
(4.5°C)
7
30min
Summary of Contents for AM***NN4*CH Series
Page 39: ...39 English Appendix Memo ...
Page 40: ......