Base construction and installation of the outdoor unit
Foundation
<When installing on the ground>
Draining Ditch
Over 150 mm
Outdoor unit installation
Base ground
Foundation (or H beam
or anti-vibration frame)
Outdoor unit
Anchor bolt
nut, Spring washer
Foundation (or H beam or anti-
vibration frame)
Anti-vibration pad
Over A + 10~20 mm
A
20 mm
50 mm or
mor
e
Inser
tion
depth
Fixing the outdoor unit
A
B
54
C
D
54
Hole on outdoor unit for fixing anchor bolt (4 - Ø12)
Foundation (or H beam or anti-vibration frame)
(Unit : mm)
Classification
Small type
Large type
Models
AM080/100/120MXWA
✴✴
AM200MXWA
✴✴
/AM300KXWA
✴✴
A
770
1100
B
656
995
C
523
515
D
550
550
❋
❋
For adding the anti-vibration frame on the base ground, the specification for the fixing hole depends on the specification