35
English
Ins
tallation par
t
4
Pass the drain hose under the refrigerant pipe, keeping
the drain hose tight.
5
Pass the drain hose through the hole in the wall. Check
if it slants downwards as seen in the picture.
NOTE
•
The hose will be fixed permanently into position after
finishing the installation and the gas leak test; refer to
page 12 for further details.
•
DO NOT WALL UP THE DRAIN HOSE CONNECTION!
Drain hose connection must be easy accessible and
serviceable.
Optional: Changing direction of the
drain hose
You can select the direction of the drain hose, depending
on where you want to install the indoor unit.
1
Detach the rubber cap with the flyer.
Drain hose
Screw hole
Screw
2
Detach the drain hose by pulling it and turning to the left.
3
Insert the drain hose by fixing it into the groove of the
drain hose and the outlet of the drain pan.
Drain pan
outlet
Rubber cap
4
Attach the rubber cap with a screwdriver by turning it
to the right until it fixes to the end of the groove.
Connecting the power and
communication cables
1
Before wiring work, you must turn off all power
source.
2
Indoor unit power should be supplied through the
breaker( ELCB or MCCB+ELB ) separated by the
outdoor power.
•
ELCB:Earth Leakage Circuit Breaker
•
MCCB:Molded Case Circuit Breaker
•
ELB:Earth Leakage Breaker
3
The power cable should be used only copper wires.
4
Connect the power cable{1(L), 2(N)} among the units
within maximum length and communication cable(F1,
F2) each.
5
Cut the cable as like the following picture. The earth
cable need to be longer than the power cable (1(L),
2(N)) by 100 mm.
100mm
6
Connect the earth cable to the plate on the evaporator
as like the following picture.
Power-earth
cable
DVM_BORACAY_IB_DB68-06415A-00_EN.indb 35