When installing more than 1 outdoor unit
Unit: mm (inch)
❋
❋
When 3 sides of the outdoor unit are blocked by the wall
300 (12) or
mor
e
300 (12) or
more
600 (24) or
more
600 (24) or
more
600 (24) or
more
❋
❋
When the walls are blocking front and the rear of the outdoor units
300 (12) or
mor
e
1500 (60) or
mor
e
600 (24) or more
600 (24) or more
❋
❋
When front and rear side of the outdoor unit is toward the wall
1500 (60) or
more
600 (24) or
more
3000 (120) or
more
300 (12) or
more
3000 (120) or
more
• Should adopt bar type louver . Don’t use a type of rain resistance louver .
[Bar type louver]
[Rain resistance louver]
• Louver specifications .
- Angle criteria : less than 20˚
- Opening ratio criteria : greater than 80%