40
Setting outdoor unit option switch and key function
X
X
K9, K10:
Silent mode
option . This reduces FAM RPM to operate the outdoor unit quietly during night operation .
Switch
Function (Silent mode)
K9
K10
ON
ON
Disuse Silent mode
ON
OFF
STEP - 1
OFF
ON
STEP - 2
OFF
OFF
STEP - 3
❋
❋
Enables the silent mode for night-time in cooling mode . (It operates automatically depending on the temperature .)
❋
❋
However, if the external contact interface module (MIM-B14) is used, entering the silent mode is available with contact
signal in cooling and heating mode .
X
X
K11, K12: Changing heating capacity correction table
Switch
Function
K11
K12
ON
ON
Default
ON
OFF
Default - 28 .4 psi
OFF
ON
Default - 14 .2 psi
OFF
OFF
D 14 .2 psi
❋
❋
Heating operation increases frequency when current high pressure is higher than target high pressure; vice versa,
decreases frequency . When target high pressure is high, the discharge air temperature of an indoor unit will increase but
energy consumption will increase as well .
❋
❋
Maintaining factory default status is recommended . However, if you want to reduce energy consumption or you are not
satisfied with heating performance, control the operation according to the surrounding environment . As you decrease
the target high pressure, energy consumption and noise may decrease but indoor air discharge temperature decreases
as well .
X
X
K13, K14: Changing current limit option table
Switch
Function
K13
K14
3 ton
4 ton
5 ton
ON
ON
Default
Default
Default
ON
OFF
Maximum current - 4(A)
Maximum current - 2(A)
Maximum current - 2(A)
OFF
ON
Maximum current - 6(A)
Maximum current - 4(A)
Maximum current - 4(A)
OFF
OFF
Maximum current - 8(A)
Maximum current - 6(A)
Maximum current - 6(A)
Classification
Model
Maximum current
3Ton
AM036FXMDCH
✴
22A
4Ton
AM048FXMDCH
✴
24A
5Ton
AM053FXMDCH
✴
32A