4-3 CONTROL KIT & wired remote controller errors
- If an error occurs, ( ) icon will be displayed on the wired remote controller.
- Press the Test button to see the error code.
Display
Explanation
Error Source
101
CONTROL KIT / OUTDOOR UNIT wire connection error
CONTROL KIT, OUTDOOR UNIT
162
EEPROM Error
CONTROL KIT
198
Error of Terminal Block’s Thermal Fuse(Open)
CONTROL KIT
201
CONTROL KIT/OUTDOOR UNIT communication error (Matching error)
CONTROL KIT, OUTDOOR UNIT
202
CONTROL KIT/OUTDOOR UNIT communication error (3 min)
CONTROL KIT, OUTDOOR UNIT
203
Communication error between INVERTER and MAIN MICOM (6 min)
OUTDOOR UNIT
221
OUTDOOR UNIT temperature sensor error
OUTDOOR UNIT
231
condenser temperature sensor error
OUTDOOR UNIT
251
Discharge temperature sensor error
OUTDOOR UNIT
320
OLP sensor error
OUTDOOR UNIT
403
Detection of OUTDOOR UNIT compressor freezing (During cooling operation)
OUTDOOR UNIT
404
Protection of OUTDOOR UNIT when it is overload (during Safety Start, Normal operation state)
OUTDOOR UNIT
407
Comp down due to high pressure
OUTDOOR UNIT
416
Discharge of a compressor is overheated
OUTDOOR UNIT
425
Power source line missing error (only for 3-phase model)
OUTDOOR UNIT
440
Heating operation blocked (outdoor temperature over 35°C)
OUTDOOR UNIT
441
Cooling operation blocked (outdoor temperature under 9°C)
OUTDOOR UNIT
458
OUTDOOR UNIT fan1 error
OUTDOOR UNIT
461
[Inverter] Compressor startup error
OUTDOOR UNIT
462
[Inverter] Total current error/PFC over current error
OUTDOOR UNIT
463
OLP is overheated
OUTDOOR UNIT
464
[Inverter] IPM over current error
OUTDOOR UNIT
465
Compressor V limit error
OUTDOOR UNIT
466
DC LINK over/low voltage error
OUTDOOR UNIT
467
[Inverter] Compressor rotation error
OUTDOOR UNIT
468
[Inverter] Current sensor error
OUTDOOR UNIT
469
[Inverter] DC LINK voltage sensor error
OUTDOOR UNIT
470
EEPROM Read/Write error
OUTDOOR UNIT
471
[Inverter] OTP error
OUTDOOR UNIT
474
IPM(IGBT Module) or PFCM temperature sensor Error
OUTDOOR UNIT
475
OUTDOOR UNIT fan2 error
OUTDOOR UNIT
484
PFC Overload Error
OUTDOOR UNIT
485
Input current sensor error
OUTDOOR UNIT
500
IPM is overheated
OUTDOOR UNIT
554
Gas leak error
OUTDOOR UNIT
590
Inverter EEPROM Checksum error
OUTDOOR UNIT
601
Communication error between the CONTROL KIT and wired remote controller
Wired Remote Controller
602
Wired remote controller Master/Slave setting error
Wired Remote Controller
604
Communication tracking error between the CONTROL KIT and wired remote controller
CONTROL KIT, Wired Remote Controller
607
Communication error between the Master and Salve wired remote controllers
Wired Remote Controller
901
Water inlet (PHE) temperature sensor error(open/short)
OUTDOOR UNIT
902
Water outlet (PHE) temperature sensor error(open/short)
OUTDOOR UNIT
903
Water outlet (backup heater) temperature sensor error.
CONTROL KIT
904
DHW tank temperature sensor error
CONTROL KIT
906
Outdoor Eva Inlet Temp Sensor (open/short)
OUTDOOR UNIT
911
Flow switch and water pump error (F/S signal is OFF for 10 sec. during the water pump signal is
ON)
CONTROL KIT
912
Flow switch and water pump error (Water pump signal is OFF for 60sec during the F/S signal is
ON)
CONTROL KIT
916
Mixing valve temp sensor (open/short)
CONTROL KIT
NOTE
When the product does not work during or after the concrete curing function and it displays “CC” on the wired remote controller, contact the installer to
cancel the concrete curing function.