Product Specifications
12
Samsung Electronics
Model
AM028HNNDEH/TL
AM036HNNDEH/TL
AM045HNNDEH/TL
Power Supply
1,2,220-240,50
1,2,220-240,50
1,2,220-240,50
Mode*1)
HP/HR
HP/HR
HP/HR
Performance
Capacity
(Nominal)
Cooling*2)
kW
2.8
3.6
4.5
Btu/h
9,600
12,300
15,400
Heating*3)
kW
3.2
4
5
Btu/h
10,900
13,600
17,100
Power
Power Input
(Nominal)
Cooling*2)
W
120
120
120
Heating*3)
120
120
120
Current Input
(Nominal)
Cooling*2)
A
0.87
0.87
0.89
Heating*3)
0.87
0.87
0.89
Fan
Motor
Type
-
Turbo Fan
Turbo Fan
Turbo Fan
Output
W
40 x 1
40 x 1
40 x 1
Air Flow Rate
H/M/L (UL)
CMM
11.8/10.8/9.8
12/11/10
13/12/11
External
Pressure
Min / Std / Max
mmAq
-
-
-
Pa
-
-
-
Piping
Connections
Liquid (Flare)
ø, mm
6.35
6.35
6.35
ø, inch
1/4"
1/4"
1/4"
Gas (Flare)
ø, mm
12.70
12.70
12.70
ø, inch
1/2"
1/2"
1/2"
Drain (Quick Lock)
ø, mm
VP25 (OD 32,ID 25)
VP25 (OD 32,ID 25)
VP25 (OD 32,ID 25)
Field
Wiring
Power Source Wire
mm²
2.5
2.5
2.5
Transmission Cable
mm²
VCTF 0.75 ~ 1.5
VCTF 0.75 ~ 1.5
VCTF 0.75 ~ 1.5
Refrigerant
Type
-
R410A
R410A
R410A
Control Method
-
EEV INCLUDED
EEV INCLUDED
EEV INCLUDED
Sound
Sound Pressure
H/M/L
dBA
40 / 36 / 34
40 / 36 / 34
43 / 41 / 38
Dimensions
Net Weight
ΜΘ
16.0
16.0
16.0
Shipping Weight
ΜΘ
18.4
18.4
18.4
Net Dimensions (W x H x D)
ΞΞ
575 x 260 x 575
575 x 260 x 575
575 x 260 x 575
Shipping Dimensions (W x H x D)
ΞΞ
669 x 339 x 644
669 x 339 x 644
669 x 339 x 644
Panel Size
Panel model
-
PC4SUSE1N
PC4SUSE1N
PC4SUSE1N
Panel Net Weight
kg
3.0
3.0
3.0
Shipping Weight
kg
5.0
5.0
5.0
Net Dimensions (W×H×D)
mm
670 x 35 x 670
670 x 35 x 670
670 x 35 x 670
Shipping Dimensions (W×H×D)
mm
723 x 117 x 723
723 x 117 x 723
723 x 117 x 723
Additional
Accessories"
Drain pump
Drain pump
- / Model
Built-in
Built-in
Built-in
Max. lifting
Height /
Displacement
mm/liter/
h
750/24
750/24
750/24
Air Filter
-
Pre filter
Pre filter
Pre filter
*1) Mode
- HP : Heat Pump, HR : Heat Recovery
*2) Nominal cooling capacities are based on;
- Indoor temperature : 27˚C DB, 19˚C WB
- Outdoor temperature : 35˚C DB, 24˚C WB, Equivalent refrigerant piping : 7.5m, Level differences : 0m
*3) Nominal heating capacities are based on;
- Indoor temperature : 20˚C DB, 15˚C WB
- Outdoor temperature : 7˚C DB, 6˚C WB, Equivalent refrigerant piping : 7.5m, Level differences : 0m
*4) Sound pressure was acquired in a dead room. Thus actual noise level may be different depending on the installation conditions.
*5) Specifications may be subject to change without prior notice for product improvement.
Indoor Unit (cont.)
Ŷ
4Way Cassette(600x600)