Auxiliary Circuit Breaker
◆
Auxiliary circuit breaker should be installed near outdoor unit so that each
access is possible.
Main/outdoor power supply cable are connected to upper/lower terminal of
auxiliary circuit breaker.
◆
It is necessary that the conduit kit for power supply to the outdoor unit be
installed between auxiliary power s/w and the outdoor unit.
(the conduit kit is optional)
Electrical Work
I
NSTALLING THE
O
UTDOOR
U
NIT
Outdoor
unit
Distribution
board
Conduit kit
Auxiliary
power
s/w
1 The supply voltage must be the same as the rated voltage of the air conditioner.
2 Prepare the power souce for exclusive use with the air conditioner.
3 Use 20 amperes time delay fuse or circuit breaker.
➢
When using the special NFB, use the NFB to bear the capacity of the
air conditioner.
➢
Otherwise, the shot circuit in the NFB may be occur.
Model
Power supply
Main power supply cable
Assembly cable
Operating current (cool/heat)
Power consumption (cool/heat)
UD18A1C2
AWG14
AWG17
7.8/7.4
1740/1640
208-230V~, 60Hz Single phase
UD26A1C2
AWG14
AWG17
12.2/13.0
2620/2800
E-
37
ENGLISH