13
English
Instal
lation Pr
oc
edur
e
3
Install the suspension bolts, depending on the ceiling
type.
Ceiling support
CAUTION
• Make sure that the ceiling is strong enough to support
the weight of the indoor unit. Before hanging the unit,
test the strength of each attached suspension bolt.
• If the length of the suspension bolt is more than
4.92ft(1.5m), vibration prevention is recommended.
If this is not possible, create an opening on the false
ceiling in order to be able to use it to perform the
required operations on the indoor unit.
4
Screw eight nuts and washers to the suspension bolts,
making space for hanging the indoor unit.
CAUTION
• You must install all of the suspension rods.
• It is important to leave sufficient space in the false
ceiling to allow access for maintenance or repairs to
the drainage pipe connection, the refrigerant pipe
connection, or to remove the unit if necessary.
5
Hang the indoor unit to the suspension bolts between
two nuts. Screw the nuts to suspend the unit.
1 way Cassette
1
2
2
4 way Cassette
Cut a pad stopper and place it on the suspension bolts to hold the washers.
Remove the stopper and screw the nuts to fix the unit.
6
Check the level of the indoor unit by using a Level.
• A tilt of the indoor unit may cause malfunction of a
built-in float switch and water leaks.
Level
7
Adjust the unit to the appropriate position, taking into
account the installation area for the front panel.
• Place the pattern sheet on the indoor unit.
• Adjust the space between the ceiling and the
indoor unit by using a Tape measure.
• Fix the indoor unit securely after adjusting the level
of the unit by using a level.
• Remove the pattern sheet and install the front
panel.
DB68-11272A-00_IM_CAC WindFree1,4way_AA_EN_.indd 13
DB68-11272A-00_IM_CAC WindFree1,4way_AA_EN_.indd 13
2021-09-17 오후 12:14:15
2021-09-17 오후 12:14:15