8
Installation Procedure
Ins
tallation Pr
oc
edur
e
English
CAUTION
ŷ
The indoor unit must be installed according to the
specified distances in order to permit accessibility
from each side, to guarantee correct operation,
maintenance, and repair of the unit.
The components of the indoor unit must be reachable
and removable under safe conditions for people and
the unit.
ŷ
Do not hold the discharge while carrying the indoor
unit to avoid the possibility of breakage.
ŷ
You must hold the hanger plate on the corner and
carry the indoor unit.
Step 3 Optional: Insulating the body
of the indoor unit
If you install a cassette type indoor unit on the ceiling
when temperature is over 27°C and humidity is over
80%, you must apply an extra 10 mm thick polyethylene
insulation or a similar type of insulation to the body of
the indoor unit.
Cut away the part where pipes are pulled out for the
insulating work.
A
Insulate the end of the pipe and some curved area by
using separate insulator.
NOTE
ŷ
A: Reference for the outer circumference of the unit
(When insulating the body of the indoor unit, use A as
the reference for its outer circumference.)
Indoor unit type and models
Dimensions
360 cassette type
<S>
(947 x 947 x 281)
AC071MN4PKH
2610 x 130
360 cassette type
<L>
(947 x 947 x 365)
AC090MN4PKH
2610 x 215
AC100MN4PKH
AC120MN4PKH
360 cassette type
<L+>
(947 x 947 x 365)
AC140MN4PKH
2610 X 215
Step 4 Installing the indoor unit
When deciding on the location of the air conditioner the
following restrictions must be taken into account.
1
Determine the positions of the pipe and the drain
hose hole as shown in the pattern sheet, and drill the
hole with an inner diameter of 14 mm.
NOTE
ŷ
Since the diagram is made of paper, it may shrink
or stretch slightly due to temperature or humidity.
For this reason, before drilling the holes, be sure
to maintain the correct dimensions between the
markings.