11
AA
ENGLISH
Connecting the cable
Two electronic cables must be connected to the outdoor unit.
The connection cord between indoor unit and outdoor unit.
The power cable between outdoor unit and auxiliary circuit breaker.
Specially for Russian and European market, before installation, the supply authority should be consulted to determine the
supply system impendance to ensure compliance.
• During the unit installation make first refrigerant connections and then electrical connections. If unit is uninstalled
first disconnect electrical cables, then refrigerant connections.
• Connect the air conditioner to grounding system before performing the electrical connection.
• When installing the unit, you shouldn't use inter connection wire.
ELCB
1
OR
Indoor Unit
Power cable
Outdoor Unit
Communication cable
Grounding
Power cable
Communication cable
Example of Air Conditioner System
When using ELCB for 1 phase
In case of extending the electric wire, please DO NOT use a round-shaped pressing socket.
- Incomplete wire connections can cause electric shock or a fire.
WARNING
Power Cable Specifications
Single Phase
The power cable is not supplied with air conditioner.
-
Select the power supply cable in accordance with relevant local and national regulations.
-
Wire size must comply with the applicable local and national code.
-
Specifications for local wiring power cord and branch wiring are in compliance with local cord.
Type of
outdoor
unit
Model
Outdoor Units
Input Current [A]
Power Supply
Outdoor Unit
Indoor Unit
Rated
Voltage Range
Outdoor (Down_Amp)
Indoor
Total
MCA
MFA
Hz
Volts
Min.
Max.
Cooling
Heating
A
AC026HCADKH
AC026HBLDKH
50
220-240
198
264
8.0
8.0
2.0
10.0
10.0
11.0
AC035HCADKH
AC035HBLDKH
50
220-240
198
264
8.0
8.0
2.0
10.0
10.0
11.0
AC035HCADKH
AC035HBMDKH
50
220-240
198
264
8.0
8.0
2.7
10.7
10.7
11.8
B
AC052HCADKH
AC052HBLDKH
50
220-240
198
264
20.0
20.0
2.0
22.0
22.0
25.0
AC052HCADKH
AC052HBMDKH
50
220-240
198
264
20.0
20.0
2.7
22.7
22.7
25.0
C
AC060HCADKH
AC060HBMDKH
50
220-240
198
264
20.0
20.0
2.7
22.7
22.7
25.0
AC071HCADKH
AC071HBLDKH
50
220-240
198
264
20.0
20.0
2.0
22.0
22.0
25.0
AC071HCADKH
AC071HBMDKH
50
220-240
198
264
20.0
20.0
2.7
22.7
22.7
25.0
AC052HCAPKH
AC052HBMPKH
50
220-240
198
264
20.0
20.0
2.7
22.7
22.7
25.0