Connecting the refrigerant pipe
Refrigerant piping system
Items
Maximum allowable length
Single installation
Type
A
Applicable outdoor unit models
AC030/036MXSCCC
Main pipe (L1)
164.0 ft (50 m)
Max. height difference between outdoor and
indoor units (h1)
98.4 ft (30 m)
indoor
outdoor
L1
h1
f
Temper grade and minimum thickness of the refrigerant pipe
Outer diameter [inch]
Minimum thickness [inch]
Temper grade
1/4
0.0276
C1220T-O
3/8
0.0276
1/2
0.0315
5/8
0.0394
5/8
0.0315
C1220T-1/2H OR C1220T-H
3/4
0.0354
7/8
0.0354
• Make sure to use C1220T-1/2H (Semi-hard) pipe for more than 3/4 in. In case of using C1220T-O (Soft) pipe for
3/4 in., pipe may be broken, which can result in an injury.
CAUTION
Make at least one round:
It will reduce noise and vibration
❋
The appearance of the unit may be different from the diagram depending on the model.
• After connecting pipes through the knock-out, cover the opening to prevent animals and debris from entering.