With the drain pump
1.
The drain pipe should be installed within 300mm to 550mm from the flexible hose and then lift down 20mm
or more.
2.
Install horizontal drainpipe with a slope of 1/100 or more and fix it by hanger space of 1.0~1.5m.
3
Install the air vent in the horizontal drainpipe to prevent water flow back to the indoor unit.
4
The flexible hose should not be installed upward position,
it may cause water flow back to the indoor unit.
1~1.5m
20mm
or more
200mm
or more
Hanger
Within
300~550mm
Air vent
300mm or less
Flexible hose
Horizontal drainpipe
more than 1/100 slope
Ceiling
• You may not need to install it if there were proper slope in
the horizontal drainpipe.
Prepare a little water about 2 liter.
1
Pour water into the base pan in the indoor unit as shown in figure.
2
Confirm that the water flows out through the drain hose.
Testing the drainage
Installing DPM
i
Only AC035HBMDKH, AC052HBMDKH, AC060HBMDKH, AC071HBMDKH models are available to install DPM.
◆
When installing DPM,you should set "DPM setting" to the outdoor unit.
◆
If DPM model is not set,communication error may occur.
◆
While the outdoor unit is tracking the indoor unit for one minute after the power supply is turned on.the operation may
stop if the remote control reception signal of the installed indoor unit is different.
◆
When DPM is installed, Automatic Air-Volume function cannot be performed simultaneously for all indoor units. Automatic
Air-Volume function must be performed for each indoor unit with the wired remote control attached.