Testing operations
1 . Check the power supply between the outdoor unit and the auxiliary circuit breaker .
f
f
1 phase power supply : L1, L2
2 . Check the indoor unit .
1) Check that you have connected the power and communication cables correctly . (If the power cable and
communication cables one mixed up or connected incorrectly, the PCB will be damaged .)
2) Check the thermistor sensor, drain pump/hose, and display are connected correctly .
3 . Press K1 or K2 on the outdoor unit PCB to run the test mode and stop .
f
f
Press K1 button
Start Heating test mode
Press K1 button
Stop
Heating test mode 7-seg display :
f
f
Press K2 button
Start Cooling test mode
Press K2 button
Stop
Cooling test mode 7-seg display :
f
f
Press K1 button twice
Start Defrost test mode
Press K1 button
Stop
Defrost test mode 7-seg display :
Condition 1 : The outdoor temperature is under 50 °F
Condition 2 : All the temperature conditions should meet the defrost conditions
ON
1 2 3 4
4 . After 12 minutes of stationary condition check each indoor unit air treatment :
f
f
Cooling mode(indoor unit check)
Inlet air temp . - Outlet air temp . : From 50 °F to 53 .6 °F
f
f
Heating mode(indoor unit check)
Outlet air temp . - Inlet air temp . : From 51 .8 °F to 57 .2 °F
f
f
In heating mode, the indoor fan motor can remain off to avoid cold air blown into conditioned space .
5 . How to reset the power supply of the outdoor unit and deactivate the eco mode (standby mode) :
f
f
Press [K3] button over 1 sec to reset the power supply of the outdoor unit and deactivate the eco mode (standby mode) .
6 . View Mode : When the K4 switch is pressed, you can see information about our system state as below .
Short
push
Display contents
SEG1
SEG2
SEG3
SEG4
Unit
1
Order frequency
1
Hundreds' digit Tens' digit
Unit digit
Hz
2
Current frequency
2
Hundreds' digit Tens' digit
Unit digit
Hz
3
The number of current indoor units
3
Hundreds' digit Tens' digit
Unit digit
EA
4
The sensor for outdoor air intake
4
+ / -
Tens' digit
Unit digit
°C
5
Discharge sensor
5
Hundreds' digit Tens' digit
Unit digit
°C
6
Eva-Mid sensor
6
+ / -
Tens' digit
Unit digit
°C
7
Cond sensor
7
+ / -
Tens' digit
Unit digit
°C
8
Current
8
Tens' digit
Unit digit
The first place of
decimals
A
9
Fan RPM
9
Thousands'
digit
Hundreds' digit
Tens' digit
rpm
10
Target discharge temperature
A
Hundreds' digit Tens' digit
Unit digit
°C
11
EEV
B
Hundreds' digit Tens' digit
Unit digit
step
12
The capacity sum of indoor units
C
Tens' digit
Unit digit
The first place of
decimals
kW