3. Capacity Table
Outdoor units
TC : Total Capacity, PI : Power Input
Cooling
Heating
Outdoor
Temp.
(℉, DB)
Indoor Temperature (℉, DB / WB)
68 / 57
72 / 61
77 / 64
80 / 67
82 / 70
86 / 72
90 / 75
TC
SHC
PI
TC
SHC
PI
TC
SHC
PI
TC
SHC
PI
TC
SHC
PI
TC
SHC
PI
TC
SHC
PI
MBH MBH kW MBH MBH kW MBH MBH kW MBH MBH kW MBH MBH kW MBH MBH kW MBH MBH kW
-4
19.60 18.27 1.91 25.55 20.16 2.50 30.10 23.53 3.05 35.00 25.10 3.70 37.80 24.67 3.93 39.20 26.14 3.99 41.30 26.95 4.06
70
26.04 22.28 1.87 33.95 24.57 2.43 39.99 28.68 2.97 46.50 30.60 3.60 50.22 30.07 3.82 52.08 31.87 3.88 54.87 32.86 3.95
95
24.01 21.04 2.09 30.35 23.14 2.60 38.05 28.00 3.33 36.00 27.00 3.43 50.74 30.20 4.64 52.10 32.06 4.71 54.81 33.00 4.78
115
23.73 20.19 3.48 28.93 21.62 4.03 30.88 23.76 4.06 32.50 24.05 4.10 34.45 22.94 4.14 35.75 24.87 4.17 36.73 25.55 4.14
126
17.96 16.11 2.71 21.89 17.25 3.12 23.37 18.96 3.14 24.60 19.19 3.17 26.08 18.31 3.20 27.06 19.84 3.22 27.80 20.38 3.20
TC : Total Capacity, SHC : Sensible Heat Capacity, PI : Power Input
Outdoor
Temp.
(℉, DB)
Indoor Temperature (℉, DB)
61
64
68
70
72
75
TC
PI
TC
PI
TC
PI
TC
PI
TC
PI
TC
PI
MBH
kW
MBH
kW
MBH
kW
MBH
kW
MBH
kW
MBH
kW
-13
26.16
3.97
25.91
4.03
25.65
4.12
25.40
4.16
25.15
4.20
24.89
4.23
-4
33.17
4.49
32.84
4.56
32.52
4.65
32.20
4.70
31.88
4.75
31.56
4.79
5
39.04
4.90
38.66
4.97
38.28
5.07
37.90
5.13
37.52
5.19
37.14
5.22
14
41.92
4.77
41.51
4.84
41.11
4.80
40.70
4.87
40.29
4.90
39.89
4.80
32
43.98
3.78
43.55
3.94
43.13
4.14
42.70
4.17
42.27
4.18
41.85
4.27
47
43.57
3.14
43.16
3.24
42.74
3.34
34.60
3.36
39.87
3.31
39.05
3.16
75
55.06
3.46
51.42
3.24
47.78
2.97
45.50
2.82
42.77
2.72
39.59
2.58
ꞏ CXH36UPB (AC036BXUPCH/AA)
•
The performance table shows the average value of each conditions.