Troubleshooting
4-20
Samsung Electronics
Option
SEG13
SEG14
SEG15
SEG16
Explanation
PAGE
Use of external control
Setting the output of external
control
RESERVED
Indication and
Details
ndication
Details
ndication
Details
ndication
Details
2
0
Disuse
Sub,
Existing
Control
0
Thermo on
1
On/Off
2
Off
3
Window
4
Disuse
Main,
Existing
Control
5
On/Off
6
Off
7
Window
8
Disuse
Sub,
Reverse
Control
1
Operation
on
9
On/Off
A
Off
B
Window
C
Disuse
Main,
Reverse
Control
D
On/Off
E
Off
F
Window
Option
SEG17
SEG18
SEG19
SEG20
Explanation
Buzzer control
Maximum filter usage time
2)
PAGE
Individual control with remote
control
3)
Indication and
Details
Indication
Details
Indication
Details
Indication
Details
Indication
Details
0
Use of buzzer
2
1000 Hour
3
0 or 1
Indoor1
1
Disuse
6
2000 Hour
2
Indoor2
3
Indoor3
4
Indoor4
Option
SEG21
SEG22
SEG23
SEG24
Explanation
Heating setting
compensation
4)
RESERVED
Away Set OFF Timer
RESERVED
Indication and
Details
Indication
Details
Indication
Details
0
Disuse
0 or 1
Auto Set OFF 30Min.
1
3.6°F(2°C)
2
Auto Set OFF 60Min.
2
9°F(5°C)
3
Auto Set OFF 120Min.
4
Auto Set OFF 180Min.
•1) SEG4
By SEG4 setting, Minimizing fan operation when thermostat is off.
- Fan operates for 20 seconds at an interval of 5 minutes in heat mode.
- Fan stops or operates Ultra low in Cooling when thermostat is off.
• 2) SEG18
If you set the Maximum filter usage time option to a value other than 2 and 6, it is automatically set to 2 (1000 hours).
• 3) SEG20
If you set the Individual control with remote control option to a value other than 0 to 4, it is automatically set to 0 (Indoor 1)
• 4) SEG21
Default value of Heating setting compensation is 3.6°F(2℃).