Troubleshooting
Samsung Electronics
4-45
Option item
Input unit
SEG1
SEG2
SEG3
SEG4
Function
Channel address
Main
0
0
A
U
Automatic setting (Factory default)
00~15
Manual setting
Snow accumulation
prevention control
Main
0
1
0
0
Disabled (Factory default)
0
1
Enabled
Step for Silence mode
Main
0
2
0
0
Disabled (Factory default)
0
1
Step1
0
2
Step2
0
3
Step3
Type of Silence mode
Main
0
3
0
0
Automatic Silence mode
(Factory default)
0
1
Manual Silence mode
Temperature unit
Main
0
4
0
0
Celsius (default)
0
1
Fahrenheit
Not applicable
Main
0
5
0
0
Not applicable
0
1
Not applicable
Current restriction rate
¹
⁾
Main
0
6
0
0
100%
(Factory default)
0
1
95%
0
2
90%
0
3
85%
0
4
80%
0
5
75%
0
6
70%
0
7
65%
0
8
60%
0
9
55%
1
0
50%
1
1
100%
Dedicated mode
for cooling/ heating
²⁾
Main
0
7
0
0
Cooling / Heating operation (default)
0
1
Cooling operation only
0
2
Heating operation only
• 1) Current restriction rate : When restriction option is set, cooling and heating performance may decrease.
• 2) AC***BXSCCC models are cooling-only models and do not support heating mode.
These models operate in cooling mode only, even if "heating operation only" mode is enabled.