
30
Installation Procedure
English
Installation Pr
oc
edur
e
2
Set an address for each indoor unit using the remote control, according to your air conditioning system plan, by
referring to the following table and by following the steps in
Common steps for setting the addresses and options
on page
18
.
• The indoor unit addresses (main and RMC addresses) are set to
0A0000-100000-200000-300000
by default.
• If indoor units and outdoor units match 1:1, you don’t need to set the main address because it is automatically set
by the outdoor unit.
• If you are using on or off controller, set RMC address.
Option
SEG1
SEG2
SEG3
SEG4
SEG5
SEG6
Function
Page
Mode
Setting main
address
Reserved
Indoor unit
number
Indoor unit
number
Indication
and
details
Indication
Details
Indication
Details
Indication
Details
Indication
Details
Indication
Details
0
A
0
No main
address
0 to 1
Tens
digit
0 to 9
Units
digit
1
Main
address
setting
mode
Option
SEG7
SEG8
SEG9
SEG10
SEG11
SEG12
Function
Page
Reserved
Setting RMC
address
Reserved
Group channel
(x16)
Group address
Indication
and
details
Indication
Details
Indication
Details
Indication
Details
Indication
Details
1
0
No RMC
address
RMC1
0 to 2
RMC2
0 to F
1
RMC
address
setting
mode
CAUTION
• The main address must be set to a value in the range 0 to 14. If you set other values, communication error will occur.
• If any of SEG5 and SEG6 is set to a value in the range A to F, the main address of the indoor unit does not change.
• If SEG3 is set to 0, the indoor unit maintains the existing main address even if SEG6 is set to a new value.
• If SEG9 is set 0, the indoor unit maintains the existing RMC address even if SEG11 and SET12 are set to new values.
Summary of Contents for AC TN4PKC Series
Page 38: ......