23
ENGLISH
CAUTION
t
Select the power cable in accordance with relevant local and national regulations.
t
Wire size must comply with local and national code.
t
Power supply cords of parts of appliances for outdoor use shall not be lighter than polychloroprene sheathed
øJYJCMFDPSE $PEFEFTJHOBUJPO)3/'PS)3/'t:PVTIPVMEDPOOFDUUIFQPXFSDBCMFJOUPUIFQPXFS
cable terminal and fasten it with a clamp.
t
The unbalanced power must be maintained within 10 % of supply rating among whole indoor units.
t
If the power is unbalanced greatly, it may shorten the life of the condenser. If the unbalanced power is
exceeded over 10% of supply rating, the indoor unit is protected, stopped and the error mode indicates.
t
To protect the product from water and possible shock, you should keep the power cable and the connection
cord of the indoor and outdoor units in conduit.
t
You must keep the cable in a protective conduit.
t
Keep distances of 2” (50 mm) or more between power cable and communication cable.
t
Maximum length of power cables are decided within 10% of power drop. If it exceeds, you must consider
another power supplying method.
t
Use round pressure/crimp terminal for connections to the power terminal block.
t
For wiring, use the designated power cable and connect it firmly, then secure to prevent outside pressure
being exerted on the terminal board.
t
Use an appropriate screwdriver for tightening the terminal screws.
A screwdriver with a small head will strip the head and make proper tightening impossible.
t
Over-tightening the terminal screws may break them.
t
See the table below for tightening torque for the terminal screws.
Tightening torque
/tN
MCGtGU
M3.5
0.8~1.2
0.59~0.89
M4
1.2~1.8
0.89~1.33