Troubleshooting
INST
ALLA
TION P
A
R
TS
No.
Error
Code
Meaning
Remarks
20
E348
Lock error on Fan2 of outdoor unit
Fan2 error
21
E353
Error due to overheated motor of outdoor unit's Fan2 Fan2 error
22
E355
Error due to overheated IPM of Fan2
Fan2 error
23
E378
Error due to overcurrent of Fan2
Fan2 error
24
E386
Over-voltage/low-voltage error of Fan2
Fan2 error
25
E387
Hall IC connection error of Fan2
Fan2 error
26
E389
V-limit error on Fan2 of compressor
Fan2 error
27
E391
Error due to DataFlash of Fan2
Fan2 error
28
E393
Output current sensor error of Fan2
Fan2 error
29
E396
DC voltage sensor error of Fan2
Fan2 error
30
E399
Heat sink temperature sensor error of Fan2
Fan2 error
31
E403
Compressor down due to freeze protection control
Check Outdoor Cond.
32
E404
System stop due to overload protection control
Check Comp. when it start
33
E416
System stop due to discharge temperature
-
34
E422
Blockage detected on high pressure pipe
1. Check if the service valve is open
2. Check for refrigerant leakage(pipe
connections, heat exchanger) and
charge refrigerant if necessary
3. Check if there's any blockage on
refrigerant cycle(indoor unit/outdoor unit)
4. Check if additional refrigerant has
been added after pipe extension
35
E425
Reverse phase or open phase
Check whether 3 phase is reversed or
opened.
36
E440
Heating mode restriction due to high air temperature
Heating
37
E441
Cooling mode restriction due to low air temperature
Cooling
38
E446
Error due to operation failure of Fan1
Fan1 error
39
E447
Motor wire of Fan1 is not connected
Fan1 error
40
E448
Lock error on Fan1 of outdoor unit
Fan1 error
41
E452
Error due to ZCP detection circuit problem or power
failure
-
42
E453
Error due to overheated motor of outdoor unit's Fan1 Fan1 error
43
E455
Error due to overheated IPM of Fan1
Fan1 error
44
E458
Fan speed error
Fan1 error
45
E461
Error due to operation failure of inverter compressor
-
46
E462
System stop due to full current control
-