64
EB 8389S EN
ST
AR
T-UP
Step response settings:
Step start, Step end, Tolerance limit of step response,
Settling time before test start, Delay time after step, Scan rate, Number of step
responses
Activation of the ramp function
*
Note!
T
he posit
ioner is write-pr
otected when tests ar
e per
for
med ac
cor
ding to a schedule (local oper
at
ion and oper
at
ing softwar
e).
â
â
â
100
90
x [%]
t [s]
x [%]
No
Yes
100
90
x [%]
t [s]
â
Ramp time (rising)
Ramp time (falling)
â
Cancelation conditions
Max. test duration
x control value
delta y-monitoring
value
PST tolerance band
Status classification (NE 107)
PST/FST
Maximum test
duration
exceeded or the
valve has not
moved before
reaching the
max. breakaway
time.
â
The valve position
exceeds 'x control
value'.
â
The drive signal
exceeds the
comparative value
given by the delta
y-monitoring.
â
The valve
position
deviation
exceeds the
PST tolerance
band.
â
â
Observe start conditions
(see
u
page 68 and page 68)!
â
Auto test time
â
â
Target PST testing mode
â
â
PST Man
PST Auto*
â
Start test
â
â
Other cancelation causes: Solenoid valve
triggered/forced venting active; Supply
pressure too low; Too much friction; Step start
too large; Change in set point; Current too low
First PST after defining parame
-
ters =
Reference
Other cancelation causes: Solenoid valve
triggered/forced venting active; Supply
pressure too low; Too much friction; Step start
too large; Change in set point; Current too low
TES
T/PROCESS
â
Start further PST
â
â
â
â
â
â
â
Analysis (NE 107)/logged by operating hours counter
PST/FST
â
Reset PST
Tests –
Partial stroke test (PST)