EB 8389S EN
63
Tests
The 'Test information' status indicates
'Test active'. 'd3' and 'tEST' are indicated
in alternating sequence on the positioner
display. 'Function check' is activated
as the condensed state.
1.
Operation > Operating mode
−
Target mode (Code 0): Manual
2.
Diagnosis > Tests > Static characteristic
−
Start: 0.0 to 100.0 %, [50.0 %]
−
End: 0.0 to 100.0 % [52.0 %]
−
Delay time after step:
0.1 to 25.0 s, [1.0 s]
−
Number of measurement values until turn
back: 1 to 50, [50]
3.
−
Start test
Note:
Cancel the test by right-clicking 'Stop
test' and selecting 'Execute' or by
pressing the rotary pushbutton at the
positioner.
After the test has been canceled, the posi-
tioner remains in manual mode.
In TROVIS-VIEW the test information and
progress flag of the test are displayed. The
'Test information' status indicates 'Test not
active' after the test is finished.
4.3.1
Resetting single status
messages
A single reset of diagnostic parameters and
measured data is not possible.