Automation System TROVIS 5500
Heating and District Heating Controller
TROVIS 5575

Mounting and
Operating Instructions

EB 5575 EN

Firmware version 1.6x
Edition January 2007

®

Electronics from SAMSON 

Summary of Contents for TROVIS 5575

Page 1: ...Automation System TROVIS 5500 Heating and District Heating Controller TROVIS 5575 Mounting and Operating Instructions EB 5575 EN Firmware version 1 6x Edition January 2007 Electronics from SAMSON...

Page 2: ...ly claims for compensation including lost profits or any other financial loss except the damage was caused intentionally or by gross negligence If an essential term of the contract is breached by negl...

Page 3: ...deactivating functions 23 2 3 Changing parameters 25 2 4 Calibrating the sensors 26 2 5 Resetting to default values 27 3 Manual operation 28 4 Systems 29 5 Functions of the heating circuit 50 5 1 Wea...

Page 4: ...ide functions 74 7 1 Automatic summer time winter time changeover 74 7 2 Frost protection 74 7 3 Forced operation of the pumps 75 7 4 Return flow temperature limitation 75 7 5 Condensate accumulation...

Page 5: ...90 8 3 Temperature monitoring 91 9 Memory module 92 9 1 Data logging 92 10 Installation 93 11 Electrical connection 96 12 Appendix 102 12 1 Function block lists 102 12 2 Parameter lists 114 12 3 Assi...

Page 6: ...ion TROVIS 5575 000x Standard controller with illuminated display background and with device bus TROVIS 5575 001x Controller with illuminated display background with device bus and with an additional...

Page 7: ...The operating controls are located in the front panel of the controller and protected by a Plexiglas door 1 1 1 Rotary pushbutton and changeover key Rotary pushbutton Turn q Display select parameters...

Page 8: ...Night mode reduced operation Control operation deactivated frost protection only Manual operation correction value adjusted in percent and activation deactivation of the pumps Rotary switch to adjust...

Page 9: ...ant for rated operation are used by the controller Night mode reduced operation Regardless of the programmed times of use the set points relevant for reduced operation are used by the controller Autom...

Page 10: ...2x Version without illuminated display 10 EB 5575 EN Operation STOP 1 18 2 3 6 7 8 9 4 5 10 11 12 13 14 15 16 17 19 20 Fig 1 Icons 1 Automatic operation 2 Day mode rated operation 3 Night mode reduced...

Page 11: ...oints are dis played __ __ Time Room temperature heating circuit 1 2 Outdoor temperature Temperature at flow sensor VF heating circuit 1 2 Temperature at flow sensor VF1 primary heat exchanger circuit...

Page 12: ...lay shows time q Edit the controller time Confirm the adjusted time Display shows year q Edit the year Confirm the adjusted year Display shows date day month q Edit the date Confirm the adjusted date...

Page 13: ...1 Top Heating circuit 2 Middle DHW heating Bottom Circulation pump Bottom Refer to page 121 for assignment Parameters WE Range of values Time period day 1 7 1 7 1 2 3 4 5 6 7 with 1 7 daily 1 Monday...

Page 14: ...set like the first time of use To set the times of use for each day repeat the instructions in the fields highlighted in gray Return the rotary switch to the desired operating mode left side Note Do...

Page 15: ...uits are adjusted at the rotary switches one after the other Party timer Rotary switch Position Heating circuit 1 Top Heating circuit 2 Middle DHW circuit Bottom Refer to page 121 for assignment Param...

Page 16: ...inputs 4 Info 2 The following data are shown in the same sequence as shown below Controller ID Memory capacity of data logging module section 9 1 255 Operating hours of solar circuit pump refer to se...

Page 17: ...ublic holiday Confirm public holiday To enter additional public holidays re select and repeat the steps in the fields high lighted in gray Exit data point Public holidays Note Public holidays can also...

Page 18: ...cation period Confirm start date of vacation period q Edit end of vacation period Display shows STOP day month Confirm end date of the vacation period Black squares under 1 to 4 at the top of the disp...

Page 19: ...n 2 3 Deleting vacation periods q Under Vacation periods select the start date of the period you wish to delete Confirm selection q Select Delete vacation period Note Vacation periods should be delete...

Page 20: ...ng circuit 1 Day set point Top Heating circuit 1 Night set point Top Heating circuit 2 Day set point Middle Heating circuit 2 Night set point Middle DHW circuit DHW temperature set point Bottom Refer...

Page 21: ...A4 CO7 CO1 q Operating level refer to section 1 on time display and operation Key number q Configuration and parameterization level refer to section 2 on start up PA4 PA5 CO7 CO1 CO2 PA2 Anl CO4 CO5 E...

Page 22: ...1x version has two additional hydraulic schemes Each system configuration is represented by a system code number The different schematics are dealt with in section 4 Available controller functions are...

Page 23: ...rcuit Rk2 4 CO3 Not used 4 CO4 DHW heating 4 CO5 System wide functions 4 CO6 Not used 4 CO7 Device bus Proceed as follows Switch to configuration and parameter level Display shows 0 0 0 0 q Set valid...

Page 24: ...oceed as follows Make the desired changes and confirm If applicable the next function block parameter is displayed Confirm all parameters to exit the opened function block To adjust additional functio...

Page 25: ...ide functions 4 PA6 Not used 4 PA7 Not used Proceed as follows Switch to configuration and parameter level Display shows 0 0 0 0 q Set valid key number Confirm key number Display shows PA1 q Select pa...

Page 26: ...r value must be changed such that it corresponds with a temperature value reference value measured directly at the point of measurement Sensor calibration is to be activated in CO5 via function block...

Page 27: ...ly q Select End Exit configuration level q Select End q Return to operating level 2 5 Resetting to default values All parameters in parameter levels PA1 PA2 and PA5 adjusted with the rotary switches e...

Page 28: ...torage tank charging pump Confirm selection Display blinks q Edit the correction value or activate deactivate the circulation pump etc Confirm edited settings The modified values remain active as long...

Page 29: ...lve replaces the heat exchanger in the heating DHW circuit 4 2 A storage tank charging pump replaces the primary solenoid thermoelectric valve The controller settings do not have to be changed EB 5575...

Page 30: ...nd DHW circuit include just one heat exchanger These systems are Anl 1 0 1 5 1 6 2 x 3 0 4 0 and 4 1 The boiler can be controlled by an on off output CO1 F12 0 30 EB 5575 EN Systems RK1 R F1 VF1 UP1 R...

Page 31: ...versions of TROVIS 5575 00xx Default settings CO1 F01 0 without RF1 CO1 F02 1 with AF1 CO1 F03 1 with R F1 EB 5575 EN 31 Systems BE BA AE RK WW KW SF2 ZP SLP UP1 VF1 VF4 SF1 RK1 R F1 BE BA AE RK AF1 R...

Page 32: ...see cover Not possible Note Only secondary system Default setting CO1 F01 0 without RF1 0 without RF1 0 without RF1 CO1 F02 1 with AF1 1 with AF1 1 with AF1 CO1 F03 1 with R F1 0 without R F1 1 with...

Page 33: ...System Anl 1 5 all versions of TROVIS 5575 00xx Default setting CO1 F03 1 with R F1 CO4 F01 1 with SF1 CO4 F02 0 without SF2 EB 5575 EN 33 Systems BE BA AE RK WW KW ZP SLP R F1 VF1 SF1 RK1...

Page 34: ...e Not possible ZP integration with CO4 F10 1 broken line see cover Possible Possible Note VF1 takes the position of VF4 R F1 is to be installed in the heat exchanger Default setting CO1 F03 1 with R F...

Page 35: ...System Anl 1 9 all versions of TROVIS 5575 00xx Default setting CO4 F01 0 without SF1 CO4 F03 0 without R F2 CO4 F04 0 without water flowmeter connected to terminals 03 13 EB 5575 EN 35 Systems...

Page 36: ...rsions of TROVIS 5575 00xx Default setting CO1 F01 0 without RF1 CO1 F02 1 with AF1 CO1 F03 1 with R F1 CO4 F01 1 with SF1 CO4 F02 0 without SF2 36 EB 5575 EN Systems BE BA AE RK WW KW AF1 ZP R F1 VF1...

Page 37: ...integration with CO4 F10 1 broken line see cover Not possible Default setting CO1 F01 0 without RF1 0 without RF1 0 without RF1 CO1 F02 1 with AF1 1 with AF1 1 with AF1 CO1 F03 1 with R F1 1 with R F1...

Page 38: ...all versions of TROVIS 5575 00xx Default setting CO1 F02 1 with AF1 CO1 F03 1 with R F1 CO2 F01 0 without RF2 CO2 F03 0 without R F2 38 EB 5575 EN Systems BE BA AE RK AF1 R F1 VF1 UP2 RK2 RK1 RF2 VF2...

Page 39: ...on only Default setting CO1 F02 1 with AF1 CO1 F03 1 with R F1 CO2 F01 0 without RF2 CO2 F03 0 without R F2 CO4 F01 1 with SF1 CO4 F02 0 without SF2 EB 5575 EN 39 Systems BE BA AE RK AF1 R F1 VF1 UP2...

Page 40: ...only Default setting CO1 F02 1 with AF1 CO1 F03 1 with R F1 CO2 F01 0 without RF2 CO2 F03 0 without R F2 CO4 F01 1 with SF1 CO4 F02 1 with SF2 40 EB 5575 EN Systems BE BA AE RK AF1 R F1 VF1 UP2 RK2 RK...

Page 41: ...l 3 5 all versions of TROVIS 5575 00xx Note Control and UP1 are only active during the processing of an external demand Default setting CO1 F03 1 with R F1 EB 5575 EN 41 Systems BE BA AE RK R F1 VF1 R...

Page 42: ...ns of TROVIS 5575 00xx Default setting CO1 F01 0 without RF1 CO1 F02 1 with AF1 CO1 F03 1 with R F1 CO2 F01 0 without RF2 CO2 F03 0 without R F2 42 EB 5575 EN Systems BE BA AE RK AF1 R F1 VF1 UP2 RK2...

Page 43: ...ed with the TROVIS 5575 001x version Default setting CO1 F01 0 without RF1 CO1 F02 1 with AF1 CO1 F03 1 with R F1 CO2 F01 0 without RF2 CO2 F03 0 without R F2 CO4 F01 1 with SF1 CO4 F02 0 without SF2...

Page 44: ...ed with the TROVIS 5575 001x version Default setting CO1 F01 0 without RF1 CO1 F02 1 with AF1 CO1 F03 1 with R F1 CO2 F01 0 without RF2 CO2 F03 0 without R F2 CO4 F01 1 with SF1 CO4 F02 0 without SF2...

Page 45: ...ions of TROVIS 5575 00xx Default setting CO1 F01 0 without RF1 CO1 F02 1 with AF1 CO1 F03 1 with R F1 CO2 F01 0 without RF2 CO2 F03 1 with R F2 EB 5575 EN 45 Systems BE BA AE RK AF1 R F1 VF1 UP1 RK1 R...

Page 46: ...all versions of TROVIS 5575 00xx Default setting CO1 F01 0 without RF1 CO1 F02 1 with AF1 CO1 F03 1 with R F1 CO4 F03 0 without R F2 46 EB 5575 EN Systems BE BA AE RK AF1 R F1 VF1 UP1 RK1 RK2 RF1 WW...

Page 47: ...5575 00xx Default setting CO1 F01 0 without RF1 CO1 F02 1 with AF1 CO1 F03 1 with R F1 CO4 F01 1 with SF1 CO4 F02 0 without SF2 CO4 F03 0 without R F2 EB 5575 EN 47 Systems BE BA AE RK WW KW UP1 RK1 V...

Page 48: ...575 00xx Default setting CO1 F01 0 without RF1 CO1 F02 1 with AF1 CO1 F03 1 with R F1 CO4 F01 1 with SF1 CO4 F02 1 with SF2 CO4 F03 0 without R F2 48 EB 5575 EN Systems BE BA AE RK WW KW AF1 SF2 ZP SL...

Page 49: ...of TROVIS 5575 00xx Default setting CO1 F01 0 without RF1 CO1 F02 1 with AF1 CO1 F03 1 with R F1 CO4 F01 0 without SF1 CO4 F03 0 without R F2 CO4 F04 0 without water flowmeter connected to terminals...

Page 50: ...nction of the outdoor temperature Fig 5 The outdoor temperature required for weather compensated control can either be measured at an outdoor sensor or transmitted from a connected device bus Function...

Page 51: ...ransport of the heating characteristic in upward or downward direction Outside the times of use reduced set points are used for control The reduced flow set point is calculated as the difference betwe...

Page 52: ...C 50 C 5 1 2 4 point characteristic The 4 point characteristic allows you to define your own heating characteristic It is defined by 4 points each for the Outdoor temperature the Flow temperature the...

Page 53: ...int 3 Point 4 60 C 40 C 20 C 20 C PA1 2 5 to 130 C Return flow temperature Point 1 to 4 65 C PA1 2 5 to 90 C Min flow temperature 20 C PA1 2 5 to 130 C Max flow temperature 90 C PA1 2 5 to 130 C With...

Page 54: ...g characteristic gradient and the maximum flow temperature in parameter lev els PA1 2 4 Range of values of the gradient 0 2 to1 0 4 Range of values of the maximum flow temperature 5 to 50 C In additio...

Page 55: ...the display the controller keeps the flow temperature con stant at 25 C A power failure while the drying function is active or when STOP appears on the display au tomatically leads to the drying funct...

Page 56: ...t 2 x valve transit time Heating operation is restarted immediately when the outdoor temperature falls below this value less 0 5 C hysteresis With the default settings this means that at night the sy...

Page 57: ...mes effective when the controller is in automatic mode 5 5 Delayed outdoor temperature adaptation The calculated outdoor temperature is used to determine the flow temperature set point The heat respon...

Page 58: ...set point can be in creased or reduced by up to 5 C using a continuously adjustable rotary knob When the room sensor is activated and the remote operation room panel is connected and activated the me...

Page 59: ...ng the preheating period the controller heats with the max flow temperature This temperature is built up in steps of 10 C As soon as the Day set point has been reached weather compensated control is a...

Page 60: ...low temperature set point is corrected if the Cycle time and Gain Kp are set to a value other than 0 The Cycle time determines the intervals at which the flow tem perature set point is corrected by 1...

Page 61: ...as cooled off and the room temperature is 1 C above the Set point A Gain Kp set to a value other than 0 causes a direct increase decrease in flow temperature set point when a sudden deviation in room...

Page 62: ...point the heating characteristic is modified accordingly for the following time of use The corrected value is displayed in parameter levels PA1 2 under Gradient flow Functions WE Configuration Room s...

Page 63: ...ve is opened without simultaneously operating the storage tank charging pump The storage tank charging pump is not switched on before the primary return flow temperature has reached the temperature cu...

Page 64: ...k is increased by 5 C to reach 50 C when the storage tank temperature falls below 45 C The charging temperature is calculated from the DHW temperature 45 C plus the charging temperature boost 10 C whi...

Page 65: ...ation in the schematics shown above The pre control circuit provides at least the same flow temperature as in the standard schematic version which is calculated from DHW tem perature set point Chargin...

Page 66: ...temperature T charging temperature 5 C is reached at sensor VF Note Instead of the DHW temperature parameter the Charging temperature can be adjusted as absolute value at the rotary switch if a storag...

Page 67: ...f the DHW set point and Sustained DHW temperature differ from one another Stop storage tank charging The controller stops charging the storage tank when the water temperature measured at sen sor SF2 h...

Page 68: ...ure at sensor VF is only reg ulated during the times of use of the circulation pump ZP The flowmeter or flow switch allow the controller to recognize exactly when DHW is being tapped By deleting all t...

Page 69: ...has reached the Max storage tank temperature Note The times of use of the DHW circuit do not affect the operation of the solar system After the key number 1999 has been entered the operating hours of...

Page 70: ...el operation in case of deviation 0 to 10 min Flow limit temperature for parallel pump operation 20 to 90 C 6 7 Circulation pump operation during storage tank charging With the setting CO4 F11 1 the c...

Page 71: ...stems with DHW heating and at least one heating circuit with control valve DHW heating can be given priority by applying set back operation With the setting CO4 F09 1 the temperature at the sensor VFx...

Page 72: ...erature provided disinfection has not been terminated because the Stop time has been reached If the Start time and Stop time are set to the identical time the process is controlled accord ing to the p...

Page 73: ...ol ler Functions WE Configuration Storage sensor SF1 1 CO4 F01 1 Thermal disinfection 0 3 0 00 4 00 70 C 10 C CO4 F14 1 Day of the week 1 7 1 2 7 with 1 7 every day 1 Monday 7 Sunday Start time 0 00h...

Page 74: ...stand by mode has been adjusted at the mode selector switch in all heating circuits Nevertheless the storage tank is always recharged to 10 C if the storage tank temperature falls below 5 C 4 Frost p...

Page 75: ...ing charging temperature is reduced As a result the primary flow rate is reduced and the return flow temperature falls In systems Anl 2 x and 4 1 the Max return flow temperature parameter PA4 level is...

Page 76: ...not adjusted to ascent too steeply the circulation pumps are not adjusted to run too rapidly the heating systems have been calibrated 7 5 Condensate accumulation control Activate the Limit deviation f...

Page 77: ...nd deactivating a boiler The controller switches on the boiler when the flow temperature falls below the set point by T 0 5 x hysteresis When the set point is exceeded by T 0 5 x hysteresis the boiler...

Page 78: ...r RF2 and an analog request can be matched to 0 to 10 V corresponds with 0 to 120 C flow temperature In other words flow temperature demand 12 C V Analog requests below 10 C 0 8 V input signal are not...

Page 79: ...17 1 bE 1 0 Parameter WE Parameter level Range of values Set point for binary demand processing 40 C PA1 5 to 130 C Processing of external demand 0 to 10 V Regardless of the operating mode set for con...

Page 80: ...ing for exclusive operation of the room heating 4 Max limit value DHW for exclusive operation of the DHW heating In all systems without DHW heating or without heating circuit only the Max limit value...

Page 81: ...0 1 5 1 6 3 0 3 5 4 0 and 11 x 7 10 2 Limitation using 0 4 to 20 mA signal Depending on the operating situation a heat meter at input WMZ Bed terminals 03 13 with a 0 4 to 20 mA output connected in p...

Page 82: ...ed rate status Shortly after the alert the controller closes the valve Rk1 As soon as the flow temperature falls below the set point by more than 5 C after the valve has been closed control operation...

Page 83: ...1 0 1 5 1 6 3 0 3 5 4 0 and 11 x 7 11 Device bus TROVIS 5575 002x Version without device bus The description of the device bus section 7 11 and its func tions section 7 11 1 to 7 11 6 are not relevan...

Page 84: ...ailable After the desired function blocks have been activated you must specify a reg ister number The following applies in a system of coupled controllers which are hydraulically supplied by a primary...

Page 85: ...ded when the default settings of the controller are used while stor age tank charging is active no flow temperature higher than the charging temperature is ad justed by the primary controller Neverthe...

Page 86: ...t is possible to put the heating circuits of other controllers out of operation while the DHW heating is active when the controllers are linked to one another over a device bus Control lers which shou...

Page 87: ...nnected to terminals 14 and 15 of the con troller The room panel is supplied with operating voltage terminals 1 and 2 of the room panel 12 to 26 5 V AC 15 to 36 V DC at the point of installation Funct...

Page 88: ...ister no 5 to 64 7 13 Locking manual level To protect the heating system this function can be used to lock manual level When this func tion has been activated automatic mode is started when the rotary...

Page 89: ...al key number Choose your custom key number between 0100 and 1900 Proceed as follows Switch to configuration and parameter level Display shows 0 0 0 0 q Set key number 1995 Confirm key number q Set va...

Page 90: ...yed as specified in the list below Note After the system code number has been changed any error alarms are suppressed for approx 3 minutes 8 1 Error list 4 Err 1 Sensor failure section 8 2 4 Err 2 Res...

Page 91: ...F1 2 When the return flow sensor fails the controller continues operation without return flow temperature limitation 4 Room sensors RF1 2 When the room sensor fails the controller uses the settings fo...

Page 92: ...be configured and archived on a computer 9 1 Data logging A data logging module order no 1400 9378 saves the following controller data every two minutes 4 Temperatures measured by the sensors 4 Contr...

Page 93: ...138 x 92 mm W x H in the control panel 4 Insert the controller housing through the panel cut out 5 Insert one mounting clamp 2 each at the top and bottom or at the side Screw the threaded rod towards...

Page 94: ...sh the controller upwards and pull the upper hook 5 over the top hat rail 3 Remove both screws 1 4 Pull apart the controller housing and the base 5 Install the electrical connections at the base as de...

Page 95: ...EB 5575 EN 95 Installation 1 2 2 5 3 4 5 62 15 41 57 Fig 12 Installation Wall mounting Top hat rail mounting Controller housing Panel mounting Housing base...

Page 96: ...able 10 mm using the shortest route 4 Inductances in the control cabinet e g contactor coils are to be equipped with suitable interference suppressors RC elements 4 Control cabinet elements with high...

Page 97: ...cted to an external voltage source over the terminals 25 or 28 If this is not required place a jumper from terminal 18 to terminal 25 and 28 Connecting the pumps Connect all cables with at least 1 5 m...

Page 98: ...between terminals 03 and 13 _ _ 08 09 10 11 12 13 14 15 16 17 01 02 03 04 05 06 07 UP1 SLP ZP UP2 Rk1_3 Pkt Rk2_3 Pkt Rk1_2 Pkt Rk2_2 Pkt BA9 AF1 SF1 SF2 RF2 R F2 RF1 R F1 VF1 VF2 3 4 BE1 FG1 BE2 FG2...

Page 99: ...uired between terminals 03 and 13 _ _ 08 09 10 11 12 13 14 15 16 17 01 02 03 04 05 06 07 UP1 SLP ZP Rk1_3 Pkt Rk2_3 Pkt Rk1_2 Pkt Rk2_2 Pkt BA9 AF1 SF1 SF2 RF2 R F2 RF1 R F1 VF1 VF2 3 4 BE1 FG1 BE2 FG...

Page 100: ...d between terminals 03 and 13 _ _ 08 09 10 11 12 13 14 15 16 17 01 02 03 04 05 06 07 UP1 SLP ZP UP2 Rk1_3 Pkt Rk2_3 Pkt Rk1_2 Pkt Rk2_2 Pkt BA9 AF1 SF1 SF2 RF2 R F2 RF1 R F1 VF1 VF2 3 4 BE1 FG1 BE2 FG...

Page 101: ...between terminals 03 and 13 _ _ 08 09 10 11 12 13 14 15 16 17 01 02 03 04 05 06 07 UP1 SLP ZP UP2 Rk1_3 Pkt Rk2_3 Pkt Rk1_2 Pkt Rk2_2 Pkt BA9 AF1 SF1 SF2 RF2 R F2 RF1 R F1 VF1 VF2 3 4 BE1 FG1 BE2 FG2...

Page 102: ...e Function block parameter Limiting factor 0 1 to 10 0 1 0 1 Not in Anl 1 2 04 Reserved 05 Underfloor heating Drying of jointless floors 0 Not in Anl 1 5 1 6 3 x CO1 F05 1 Limitation of the adjustment...

Page 103: ...0 to 10 min 2 min Min OFF time 0 to 10 min 2 min 13 Limitation of deviation for OPEN signal 0 All CO1 F13 1 only with CO1 F12 1 Function block parameter Max system deviation 2 to 10 C 2 C 14 Release R...

Page 104: ...0 1 0 0 3 0 4 x 04 Reserved 05 Underfloor heating Drying of jointless floors 0 All CO1 F05 1 Limitation of the adjustment ranges Function block parameters Temperature rise 1 to 10 C 24 h 5 C 24 h Maxi...

Page 105: ...transit time 5 10 15 240 s 45 s CO2 F12 0 only in system Anl 10 0 On off control Function block parameters Hysteresis 1 to 30 C 5 C Min ON time 0 to 10 min 2 min Min OFF time 0 to 10 min 2 min 13 Limi...

Page 106: ...ive Function block parameter Limiting factor 0 1 to 10 0 1 0 04 Water flowmeter 0 1 9 11 9 CO4 F04 1 option AnA bin AnA AnA Analog analysis to terminals 03 13 water flowmeter 1400 9246 bin Binary anal...

Page 107: ...peration of circulation pump during storage tank charging 0 Not Anl 1 9 11 0 11 9 CO4 F11 1 Circulation pump ZP operates according to schedule during storage tank charging CO4 F11 0 ZP switched off du...

Page 108: ...low temperature 0 1 5 1 6 2 1 2 3 3 1 4 1 CO4 F15 1 only with CO1 F03 1 16 Priority for external demand 0 1 5 1 6 2 x 3 1 3 2 4 1 With CO4 F16 1 a high external demand causes excessive charging temper...

Page 109: ...e 01 01 to 31 12 01 06 No of days until activation 1 to 3 2 Stop summer mode 01 01 to 31 12 30 09 No of days until deactivation 1 to 3 1 OT limit value summer mode 0 to 30 C 18 C 05 Delayed OT adaptat...

Page 110: ...heating 0 01 to 650 m h 3 1 5 m h 3 Max limit value DHW 0 01 to 650 m h 3 1 5 m h 3 Limiting factor 0 1 to 10 0 1 0 12 Creep feed rate limitation 0 Not in Anl 1 9 CO5 F12 1 Creep feed rate limitation...

Page 111: ...fault setting 22 Locking the rotary switches 0 All CO5 F22 1 All rotary switches are locked 23 Test mode 0 All Only for internal use Not in systems Anl 1 0 1 5 1 6 3 0 3 5 4 0 11 x F Function block nu...

Page 112: ...ler automatically searches for a room panel for which detection mode has been activated 04 TROVIS 5570 Room Panel in Rk2 0 3 x 4 x 10 0 CO2 F01 1 Communication with TROVIS 5570 active for Rk2 CO2 F01...

Page 113: ...ocessing of external demand in Rk1 using device bus Function block parameter Register no 5 to 64 5 16 Reserved 17 Send all temperature values All Not relevant for connection of several controllers 18...

Page 114: ...lel shift 30 to 30 C 0 C Min flow temperature 5 to 130 C 20 C Max flow temperature 5 to 130 C 90 C with CO1 2 F05 1 5 to 50 C 50 C applies 114 EB 5575 EN Appendix 0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15...

Page 115: ...oint 2 55 C point 3 40 C point 4 25 C 4 point characteristic Point 1 Reduced flow temperature Reduced flow temperatures of the points 2 3 4 are marked by squares below the numbers 2 3 4 5 to 130 C poi...

Page 116: ...t return flow 0 2 to 3 2 1 2 Level return flow 30 to 30 C 0 C 116 EB 5575 EN Appendix 0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 C STOP 0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 1...

Page 117: ...C Only in parameter level PA1 Set point for binary demand processing 5 to 130 C 40 C Only in parameter level PA1 EB 5575 EN 117 Appendix 0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23...

Page 118: ...temperature 5 to 90 C 60 C Hysteresis 0 to 30 C 5 C Charging temperature boost 0 to 50 C 10 C 118 EB 5575 EN Appendix 0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 C 0 1 2 3 4 5 6...

Page 119: ...e 20 to 90 C 65 C Solar pump ON 1 to 30 C 10 C EB 5575 EN 119 Appendix 0 1 2 3 4 5 6 7 8 9 1 0 11 12 13 14 15 16 17 18 19 20 21 22 23 24 STOP 4 0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21...

Page 120: ...of values default setting Public holidays 01 01 to 31 12 section 1 8 1 Vacation periods 01 01 to 31 12 section 1 8 2 120 EB 5575 EN Appendix 0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22...

Page 121: ...9 DHW heating 11 x DHW heating 2 x Heating circuit Rk1 DHW heating 3 0 Primary heat exchanger circuit and heating circuit Rk1 Rk2 3 1 and 3 2 Primary heat exchanger circuit and heating circuit Rk1 Rk...

Page 122: ...0 5 10 862 5 882 2 901 9 921 6 941 2 960 9 980 4 1000 0 1019 5 1039 0 C 15 20 25 30 35 40 45 50 55 60 1058 5 1077 9 1097 3 1116 7 1136 1 1155 4 1174 7 1194 0 1213 2 1232 4 C 65 70 75 80 85 90 95 100 1...

Page 123: ...aristor suppression TROVIS 5575 001x 4 x pump output load max 250 V AC 2A all outputs relay outputs with varistor suppression Interfaces Device bus TROVIS 5575 000x and 5575 001x RS 485 interface for...

Page 124: ...esponsible SAMSON office System code number Function block settings in the configuration levels CO 1 CO 2 CO 4 CO 5 CO 7 F01 F02 F03 F04 F05 F06 F07 F08 F09 F10 F11 F12 F13 F14 F15 F16 F17 F18 F19 F20...

Page 125: ...ced flow temperature Point 1 5 to 130 C Reduced flow temperature Point 2 5 to 130 C Reduced flow temperature Point 3 5 to 130 C Reduced flow temperature Point 4 5 to 130 C Return flow temperature Poin...

Page 126: ...12 1 5 to 240 s Hysteresis F12 0 1 to 30 C Min ON time F12 0 0 to 10 min Min OFF time F12 0 0 to 10 min Max system deviation F13 1 2 to 10 C Binary input bE F14 1 1 0 Binary input bE F17 1 1 0 Paramet...

Page 127: ...e priority in case of deviation F09 1 2 to 10 min Proportional gain KP F12 1 0 1 to 50 Reset time TN F12 1 1 to 999 s Derivative action time TV F12 1 0 s Do not change Valve transit time TY F12 1 5 to...

Page 128: ...o 31 12 Number of days until deactivation F04 1 1 to 3 OT limit value F04 1 0 to 30 C Delay F05 6 1 1 to 6 C h Frost protection limit F09 0 15 to 3 C Max limit value F10 1 3 to 500 pulse h Max limit v...

Page 129: ...s address F01 1 Auto 1 to 32 Device bus address F03 1 room panel Rk1 Auto 1 to 32 Device bus address F04 1 room panel Rk2 Auto 1 to 32 Register no F06 1 1 to 4 Register no F07 1 1 to 4 Register no F09...

Page 130: ...00 to 24 00 h Start of third time of use 0 00 to 24 00 h End of third time of use 0 00 to 24 00 h Parameters Middle rotary switch Range of values Day set point 0 5 to 40 C to 130 C Night set point 0 5...

Page 131: ...00 to 24 00 h End of second time of use 0 00 to 24 00 h Start of third time of use 0 00 to 24 00 h End of third time of use 0 00 to 24 00 h DHW circulation pump Start of first time of use 0 00 to 24...

Page 132: ...6 Default settings 27 Demand processing External 78 Using the device bus 84 Device bus 83 87 DHW heating in instantaneous heating system 68 in the storage tank charging system 66 in the storage tank s...

Page 133: ...elements 7 Operating modes 9 Operational faults 90 91 Optimization 59 Outdoor temp adaptation delayed 57 Overvoltage protection 96 P Parallel operation pumps 70 Parameter level 25 Parameter lists 114...

Page 134: ...ion 71 Summer mode 57 Summer time winter time changeover 74 Synchronizing 86 System code number 22 Systems 29 49 T Technical data 123 Temperature monitoring 91 Temperature set points 20 Thermal disinf...

Page 135: ...EB 5575 EN 135...

Page 136: ...BE BA AE RK BE BA AE RK BE BA AE RK WW WW KW SF1 ZP VF4 WW KW SF2 ZP SLP VF4 SF1 KW SF2 VF3 BA9 SF1 ZP Solar collector Type 3 Type 2 Type 1...

Page 137: ...ction block HK Heating circuit GLT Building control station Kl Terminal KW Cold water OT Outdoor temperature PA Parameter level RF Room sensor Rk Control circuit R F Return flow sensor SF Storage tank...

Page 138: ...SAMSON AG MESS UND REGELTECHNIK Weism llerstra e 3 60314 Frankfurt am Main Germany Phone 49 69 4009 0 Fax 49 69 4009 1507 Internet http www samson de 2007 05 EB 5575 EN...