EB 5573 EN
71
Functions of the heating circuit
Parameters
WE
Parameter level: value range
Flow set point, day
50.0 °C
PA1, 2: –5.0 to +150.0 °C
Flow set point, night
30.0 °C
PA1, 2: –5.0 to +150.0 °C
6.10 Adaptation
The controller is capable of automatically adapting the heating characteristic to the building
characteristics. A gradient characteristic must be set in this case (CO1, 2 > F11 - 0). The ref-
erence room, where the room sensor is located, represents the entire building and is moni-
tored to ensure that the room set point ('Day set point') is maintained. When the mean mea-
sured room temperature in rated operation deviates from the adjusted set point, the heating
characteristic is modified accordingly for the following time-of-use. The corrected value is dis-
played in PA1, 2 ('Flow gradient').
Functions
WE
Configuration
Room sensor RF1/RF2
0
CO1, 2 > F01 - 1
Outdoor sensor AF1/AF2
1
CO1, 2 > F02 - 1
Adaptation
0
CO1, 2 > F08 - 1
Four-point characteristic
0
CO1, 2 > F11 - 0
Parameters
WE
Switch position: value range
Day set point
20.0 °C
: 0.0 to 40.0 °C
Night set point
15,0 °C
: 0.0 to 40.0 °C
If the
flash adaptation
function is already configured with a small cycle time, the
adaptation
function should not be configured as well.
Note